摘要
Chillers contribute to a significant part of the building energy consumption. In order to save energy and improve the performance of building automation systems, there is an increasing need for chiller fault detection and diagnosis (FDD). This paper proposes a two-stage data-driven FDD strategy which formulates the chiller fault detection and diagnosis task as a multi-class classification problem. Linear Discriminant Analysis (LDA) is adopted to project the high dimensional data into a lower dimensional space so as to achieve maximum class separation and original class information maintenance. At the first stage, a fault is detected and diagnosed if the monitoring data set is the closest to one of the predefined fault clusters and within the predefined Manhattan distance range of the corresponding fault. At the second stage, fault severity level is recognized by comparing the monitoring data set with the corresponding predefined severity level clusters. The fault is diagnosed as at a particular severity level if it is the closest to the corresponding severity level cluster. The proposed strategy is validated by the experimental data of ASHRAE Research Project 1043 (RP-1043). Results show that the data-driven FDD strategy using LDA can detect and diagnose chiller faults effectively. (C) 2016 Elsevier B.V. All rights reserved.
引用
收藏
页码:519 / 529
页数:11
相关论文
共 35 条
[1]  
Aggarwal C.C., 2001, SURPRISING BEHAV DIS
[2]   Eigenfaces vs. Fisherfaces: Recognition using class specific linear projection [J].
Belhumeur, PN ;
Hespanha, JP ;
Kriegman, DJ .
IEEE TRANSACTIONS ON PATTERN ANALYSIS AND MACHINE INTELLIGENCE, 1997, 19 (07) :711-720
[3]   A fault detection technique for air-source heat pump water chiller/heaters [J].
Chen, Youming ;
Lan, Lili .
ENERGY AND BUILDINGS, 2009, 41 (08) :881-887
[4]  
Comstock M., ASHRAE
[5]   The sensitivity of chiller performance to common faults [J].
Comstock, MC ;
Braun, JE ;
Groll, EA .
HVAC&R RESEARCH, 2001, 7 (03) :263-279
[6]   From Model, Signal to Knowledge: A Data-Driven Perspective of Fault Detection and Diagnosis [J].
Dai, Xuewu ;
Gao, Zhiwei .
IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, 2013, 9 (04) :2226-2238
[7]   Fault detection and diagnosis based on improved PCA with JAA method in VAV systems [J].
Du, Zhimin ;
Jin, Xinqiao ;
Wu, Lizhou .
BUILDING AND ENVIRONMENT, 2007, 42 (09) :3221-3232
[8]   Detection and diagnosis for sensor fault in HVAC systems [J].
Du, Zhimin ;
Jin, Xinqiao .
ENERGY CONVERSION AND MANAGEMENT, 2007, 48 (03) :693-702
[9]   Multiple faults diagnosis for sensors in air handling unit using Fisher discriminant analysis [J].
Du, Zhimin ;
Jin, Xinqiao .
ENERGY CONVERSION AND MANAGEMENT, 2008, 49 (12) :3654-3665
[10]   Fault diagnosis for temperature, flow rate and pressure sensors in VAV systems using wavelet neural network [J].
Du, Zhimin ;
Jin, Xinqiao ;
Yang, Yunyu .
APPLIED ENERGY, 2009, 86 (09) :1624-1631