CONSIDERATIONS IN UNIT SUBSTATION DESIGN TO OPTIMIZE RELIABILITY AND ELECTRICAL WORKPLACE SAFETY

被引:0
作者
Durocher, David B. [1 ]
机构
[1] Eaton Corp, Wilsonville, OR 97070 USA
来源
2010 IEEE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS TECHNICAL CONFERENCE | 2010年
关键词
Process Industries; Power Distribution; Unit Substations; Safety by Design; Electrical Workplace Safety;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Many legacy low and medium-voltage unit substations installed today are based upon older designs that took advantage of reduced first cost "opportunities" allowed by existing installation codes and standards. Fast-forward to how these substation designs fair in safety and reliability today, particularly in industrial process applications found in cement, pulp and paper, petroleum & chemical and others, some of the exercised "opportunities" applied in the past begin to look more like liabilities than assets. Legacy engineering decisions once thought to be prudent take on new meanings today, particularly when these decisions are viewed through the lens of emerging new workplace safety standards. The critical issue of addressing destructive arc-flash hazards associated with persons working on or around energized electrical equipment must now be considered. Because traditional substation designs often appeared to involve some compromise regarding both safety and reliability, a design team of a major process industry user took a fresh look at unit substation design. The design review took place in conjunction with construction of a Greenfield plant built in the spring of 2009 in the USA. This paper will review the design limitations of traditional unit substation configurations, offer an overview of the alternatives considered by the Greenfield site project team, and discuss technical and safety validation of the design that was ultimately selected and installed. Economic comparisons to traditional designs, changes in the owner operating and safety procedures for plant personnel as a result of the engineering design changes, and overall design acceptance by operations will also be reviewed in this paper.
引用
收藏
页数:11
相关论文
共 14 条
  • [1] [Anonymous], 2009, NFPA70E
  • [2] [Anonymous], 2002, 1584 IEEE
  • [3] *ANSI, 1999, C372021999 ANSI
  • [4] *ANSI, 2001, C372032001 ANSI
  • [5] *ANSI, C3706 ANSI
  • [6] *ANSI, 2005, C5712 ANSI
  • [7] Application considerations for high resistance ground retrofits in pulp and paper mills
    Beltz, R
    Peacock, I
    Vilcheck, W
    [J]. CONFERENCE RECORD OF 2000 ANNUAL PULP AND PAPER INDUSTRY TECHNICAL CONFERENCE, 2000, : 33 - 40
  • [8] Distribution equipment modernization to reduce arc flash hazards
    Hopper, Warren S.
    Etzel, Brenda L.
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2008, 44 (03) : 940 - 948
  • [9] *IEEE, 2002, IEEE T IND APPL MAY, V38, P778
  • [10] *IEEE, 2009, IEEE IAS PCIC