Do surgeons and surgical facilities disturb the clean air distribution close to a surgical patient in an orthopedic operating room with laminar airflow?

被引:42
作者
Cao, Guangyu [1 ]
Storas, Madeleine C. A. [1 ]
Aganovic, Amar [1 ]
Stenstad, Liv-Lnger [2 ]
Skogas, Jan Gunnar [2 ]
机构
[1] Norwegian Univ Sci & Technol, Dept Energy & Proc Engn, Kolbjorn Hejes Vei 1b, N-7491 Trondheim, Norway
[2] St Olavs Hosp, Trondheim, Norway
关键词
Surgical site infection; Thermal plume; Laminar airflow; Operating room; Air velocity; Airflow distribution; Pperating microenvironment; AIRBORNE CONTAMINATION; SITE INFECTION; VENTILATION; PERFORMANCE; VELOCITY; SYSTEM; IMPACT; HIP;
D O I
10.1016/j.ajic.2018.03.019
中图分类号
R1 [预防医学、卫生学];
学科分类号
1004 ; 120402 ;
摘要
Background: Airflow distribution in the operating room plays an important role in ensuring a clean operating microenvironment and preventing surgical site infections (SSIs) caused by airborne contaminations. The objective of this study was to characterize the airflow distribution in proximity to a patient in an orthopedic operating room. Methods: Experimental measurements were conducted in a real operating room at St. Olav's Hospital, Norway, with a laminar airflow system. Omnidirectional anemometers were used to investigate the air distribution in the operating zone, and 4 different cases were examined with a real person and a thermal manikin. Results: This study showed that the downward airflow from the laminar airflow system varies in each case with different surgical arrangement, such as the position of the operating lamp. The results indicate that the interaction of thermal plumes from a patient and the downward laminar airflowmay dominate the operating microenvironment. Conclusions: The airflow distribution in proximity to a patient is influenced by both the surgical facility and the presence of medical staff. A thermal manikin may be an economical and practical way to study the interaction of thermal plumes and downward laminar airflow. The provision of higher clean airflow rate in the operating microenvironment may be an effective way to prevent the development of SSIs caused by indoor airborne contamination. (C) 2018 Association for Professionals in Infection Control and Epidemiology, Inc. Published by Elsevier Inc. All rights reserved.
引用
收藏
页码:1115 / 1122
页数:8
相关论文
共 40 条
[11]   Characterizing the Dynamic Interactions and Exposure Implications of a Particle-Laden Cough Jet with Different Room Airflow Regimes Produced by Low and High Momentum Jets [J].
Cao, Guangyu ;
Liu, Shichao ;
Boor, Brandon E. ;
Novoselac, Atila .
AEROSOL AND AIR QUALITY RESEARCH, 2015, 15 (05) :1955-1966
[12]  
Cao GY, 2017, P HLTH BUILD 2017 EU
[13]  
Chen Q., 1992, Indoor Air, V2, P154, DOI DOI 10.1111/J.1600-0668.1992.04-23.X
[14]   The integrated effect of medical lamp position and diffuser discharge velocity on ultra-clean ventilation performance in an operating theatre [J].
Chow, T. T. ;
Lin, Zhang ;
Bai, Wei .
INDOOR AND BUILT ENVIRONMENT, 2006, 15 (04) :315-331
[15]   Performance of ventilation system in a non-standard operating room [J].
Chow, TT ;
Yang, XY .
BUILDING AND ENVIRONMENT, 2003, 38 (12) :1401-1411
[16]   APPLICATION OF AERONAUTICAL TECHNIQUES TO PHYSIOLOGY .1. HUMAN MICROENVIRONMENT AND CONVECTIVE HEAT-TRANSFER [J].
CLARK, RP ;
COX, RN .
MEDICAL & BIOLOGICAL ENGINEERING, 1974, 12 (03) :270-274
[17]  
Department of Health UK, 2007, HEAT VENT SYST HLT A
[18]  
Friberg B, 1998, AORN J, V67, P841, DOI 10.1016/S0001-2092(06)62647-1
[19]   Zoned exponential, vertical and horizontal ultra-clean laminar airflows - No differences in bacteriological efficiency [J].
Friberg, BEE ;
Burman, LG ;
Friberg, S .
ACTA ORTHOPAEDICA SCANDINAVICA, 1998, 69 (02) :169-172
[20]   Influence of laminar airflow on prosthetic joint infections: a systematic review [J].
Gastmeier, P. ;
Breier, A. -C. ;
Brandt, C. .
JOURNAL OF HOSPITAL INFECTION, 2012, 81 (02) :73-78