A series active power filter adopting hybrid control approach

被引:133
作者
Wang, ZA [1 ]
Wang, Q [1 ]
Yao, WZ [1 ]
Liu, JJ [1 ]
机构
[1] Xian Jiao Tong Univ, Sch Elect Engn, Xian 710049, Peoples R China
基金
中国国家自然科学基金;
关键词
active power filter; harmonic source/load; harmonic suppression; PWM inverter;
D O I
10.1109/63.923761
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The series active power filter (APF) is suitable for compensating voltage type harmonics-producing load, whereas the control approach it adopts may directly influence its compensation characteristics. This paper first discusses the control approach of detecting source current in terms of the basic operation principle of a series APF, then developing a control approach of detecting load voltage. On the basis of these, a hybrid control approach is proposed. In this approach, the reference signal of the compensation voltage needed by the series APF is obtained by detecting both source current and load voltage. Thus, this approach has the advantages of the first and the second control approaches and at the same time, it can overcome their respective drawbacks. For practical realization, the control methods of PWM inverter in the series APF and for regulating its de side voltage are discussed in detail. A prototype of the series APF is manufactured and corresponding experiment investigation is done. The results show that when the series APF, if adopting the hybrid control approach instead of the other two, compensates for the voltage type harmonics-producing load, its performance can be improved greatly.
引用
收藏
页码:301 / 310
页数:10
相关论文
共 18 条