Characterizing gaseous air cleaner performance in the field

被引:27
作者
Howard-Reed, Cynthia [1 ]
Nabinger, Steven J. [1 ]
Emmerich, Steven J. [1 ]
机构
[1] NIST, Bldg & Fire Res Lab, Gaithersburg, MD 20899 USA
关键词
activated carbon air cleaner; building study; indoor air; model evaluation; VOC transport;
D O I
10.1016/j.buildenv.2006.03.020
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
As part of an ongoing effort to better understand the performance of indoor air cleaners in buildings, the National Institute of Standards and Technology (NIST) has completed a series of gaseous air cleaner field tests and model simulations. This paper focuses on experiments to measure the removal of decane with a sorption-based in-duct gaseous air cleaner and a sorption-based portable air cleaner in a single-zone test house. Due to the lack of standardized gaseous air cleaner field testing protocols, a field test method was developed using semi-real-time concentration measurements and mass balance analysis. A total of 24 experiments were completed with directly measured single-pass removal efficiencies ranging from 24% to 56% and removal efficiencies based on a transient whole building mass balance ranging from 30% to 44%. Experimental results revealed important factors affecting field performance such as air cleaner contaminant loading for the in-duct air cleaner and room air mixing for the portable air cleaner. An additional six tests were conducted to evaluate the predictive capability of the indoor air quality model CONTAM. Published by Elsevier Ltd.
引用
收藏
页码:368 / 377
页数:10
相关论文
共 20 条
[1]  
*AHAM, 2006, AC12006 ANSI AHAM AH
[2]  
[Anonymous], 2005, 7251 NISTIR
[3]  
ASHRAE, 2017, METH TEST GEN VENT A
[4]  
*ASHRAE, 1992, 521A ASHRAE
[5]  
*ASTM, 2003, D515703 ASTM
[6]  
*ASTM, 2001, 74100 E ASTM
[7]  
AXLEY JW, 1990, NISTGCR90573
[8]  
CHEN W, 2005, ASHRAE T, V112, P1101
[9]   INITIAL EFFICIENCIES OF AIR CLEANERS FOR THE REMOVAL OF NITROGEN-DIOXIDE AND VOLATILE ORGANIC-COMPOUNDS [J].
DAISEY, JM ;
HODGSON, AT .
ATMOSPHERIC ENVIRONMENT, 1989, 23 (09) :1885-1892
[10]   Measurement and simulation of the IAQ impact of particle air cleaners in a single-zone building [J].
Emmerich, SJ ;
Nabinger, SJ .
HVAC&R RESEARCH, 2001, 7 (03) :223-244