Mock-Up Study of the Effect of Wall Distance on the Thermal Rating of Power Cables in Ventilated Tunnels

被引:7
作者
Boukrouche, Fahd [1 ]
Moreau, Christophe [1 ]
Pelle, Julien [2 ]
Beaubert, Francois [3 ]
Harmand, Souad [2 ]
Moreau, Olivier [4 ]
机构
[1] LME, Elect France Res & Dev, F-77818 Moret Sur Loing, France
[2] Univ Valenciennes, F-59300 Valenciennes, France
[3] Univ Valenciennes, Engn Sch ENSIAME, F-59300 Valenciennes, France
[4] CIST, Elect France Grp, Dubai, U Arab Emirates
关键词
Cable rating; CFD; forced convection; Open-FOAM; radiation; turbulent flow; ventilated tunnel;
D O I
10.1109/TPWRD.2016.2629285
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Power transmission through power cables installed in ventilated tunnels is increasingly used worldwide and offers a complex thermal environment. Established correlations currently in use have been deduced from a nonfully developed turbulent flow and the effect of the proximity to a tunnel wall is not accounted for. This paper details the experimental and numerical investigations conducted on a mock-up of the heat transfer from a single cable in a fully developed turbulent airflow, with emphasis on the effect of the cable spacing from the tunnel wall. Nusselt numbers have been compared for different spacing and Reynolds numbers. The overall heat transfer is found to be meaningfully lower than in previous studies as only a third of the heat transfer is found, possible explanation of these differences are given in this paper. A threshold value is observed for the heat transfer while the cable rating depreciation is more gradual. The radiative heat exchange is found to be up to 30% of the total heat loss. An improved cooling law for the case of a single cable in tunnel taking into account the proximity of the wall has been developed from this study and confronted to the experimental and simulated data.
引用
收藏
页码:2453 / 2461
页数:9
相关论文
共 25 条
[1]  
Anders G., 2005, IEEE PRESS SERIES PO
[2]   Ampacity Calculations for Cables in Shallow Troughs [J].
Anders, George J. ;
Coates, Mark ;
Chaaban, Mohamed .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) :2064-2072
[3]   Rating of cables on riser poles, in trays, in tunnels and shafts - A review [J].
Anders, GJ .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (01) :3-11
[4]  
[Anonymous], 2006, IEC 60287-2-1
[5]  
[Anonymous], 2014, 6028721 IEC
[6]   Comparison of some inverse heat conduction methods using experimental data [J].
Beck, JV ;
Blackwell, B ;
HajiSheikh, A .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1996, 39 (17) :3649-3657
[7]   A THERMAL STUDY OF POWER CABLES COOLING IN TUNNELS [J].
Boukrouche, F. ;
Moreau, C. ;
Harmand, S. ;
Beaubert, F. ;
Pelle, J. ;
Moreau, O. .
7TH EUROPEAN THERMAL-SCIENCES CONFERENCE (EUROTHERM2016), 2016, 745
[8]  
Cigre, 1979, ELECTRA, V66
[9]  
Cigre, 1986, ELECTRA, V104
[10]  
Cigre, 1992, ELECTRA, V143