MIMO Based Decoupling Strategy for Grid Connected Power Converters Controlled in the Synchronous Reference Frame

被引:0
作者
Samanes, Javier [1 ]
Gubia, Eugenio [1 ]
Lopez, Jesus [1 ]
机构
[1] Univ Publ Navarra, Inst Smart Cities, Elect Elect & Commun Engn, Pamplona, Spain
来源
2018 IEEE 19TH WORKSHOP ON CONTROL AND MODELING FOR POWER ELECTRONICS (COMPEL) | 2018年
关键词
Converter current control. LCL-tilter; synchronous reference frame; decoupling; VOLTAGE-SOURCE CONVERTERS; DQ CURRENT CONTROL; DESIGN;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Power converters are frequently connected to the grid through a LCL filter, controlling its power transfer through a current control loop in the synchronous reference frame. In this reference frame, cross coupling terms appear between the current and voltages of the passive components, which, without a proper decoupling strategy, penalize the converter transient response and the current control adjustment. In this work, an intuitive decoupling strategy is presented to improve the dynamic behavior, based on Multiple-Input-Multiple-Output systems theory. The approach developed is particularly interesting in extremely weak grids, allowing an easier adjustment of the main controller.
引用
收藏
页数:8
相关论文
共 14 条
[1]   Multivariable-PI-Based dq Current Control of Voltage Source Converters With Superior Axis Decoupling Capability [J].
Bahrani, Behrooz ;
Kenzelmann, Stephan ;
Rufer, Alfred .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2011, 58 (07) :3016-3026
[2]   Simplified Feedback Linearization Control of Three-Phase Photovoltaic Inverter With an LCL Filter [J].
Bao, Xianwen ;
Zhuo, Fang ;
Tian, Yuan ;
Tan, Peixuan .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2013, 28 (06) :2739-2752
[3]   Overview of control and grid synchronization for distributed power generation systems [J].
Blaabjerg, Frede ;
Teodorescu, Remus ;
Liserre, Marco ;
Timbus, Adrian V. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2006, 53 (05) :1398-1409
[4]   Analysis and design of current regulators using complex vectors [J].
Briz, F ;
Degner, MW ;
Lorenz, RD .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2000, 36 (03) :817-825
[5]   Limitations of Voltage-Oriented PI Current Control of Grid-Connected PWM Rectifiers With LCL Filters [J].
Dannehl, Joerg ;
Wessels, Christian ;
Fuchs, Friedrich Wilhelm .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2009, 56 (02) :380-388
[6]   Modeling of three-phase dynamic systems using complex transfer functions and transfer matrices [J].
Harnefors, Lennart .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2007, 54 (04) :2239-2248
[7]  
IEEE, 2009, IEEEStandard1547.2-2008
[8]   Capacitor-Voltage Feedforward With Full Delay Compensation to Improve Weak Grids Adaptability of LCL-Filtered Grid-Connected Converters for Distributed Generation Systems [J].
Li, Xiaoqiang ;
Fang, Jingyang ;
Tang, Yi ;
Wu, Xiaojie ;
Geng, Yiwen .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2018, 33 (01) :749-764
[9]   Design and control of an LCL-filter-based three-phase active rectifier [J].
Liserre, M ;
Blaabjerg, F ;
Hansen, S .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2005, 41 (05) :1281-1291
[10]   Modeling and Control of N-Paralleled Grid-Connected Inverters With LCL Filter Coupled Due to Grid Impedance in PV Plants [J].
Luis Agorreta, Juan ;
Borrega, Mikel ;
Lopez, Jesus ;
Marroyo, Luis .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2011, 26 (03) :770-785