Investigations of temperature effects on the dielectric response measurements of transformer oil-paper insulation system

被引:164
作者
Saha, Tapan K. [1 ]
Purkait, Prithwiraj [2 ]
机构
[1] Univ Queensland, Sch Informat Technol & Elect Engn, Brisbane, Qld 4072, Australia
[2] HIT, Dept Elect Engn, Haldia 721657, WB, India
关键词
conductivity; depolarization current; dielectric response; dissipation factor; equivalent model; polarization current; recovery voltage; temperature; transformer insulation;
D O I
10.1109/TPWRD.2007.911123
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Dielectric testing techniques, in both time and frequency domains, are currently widely used by power utilities for assessment of the condition of transformer oil-paper insulation systems. However, it has been reported that results of these tests are highly influenced by the operating temperature during measurements. The distribution, migration and equilibrium of moisture between oil and paper in a complicated insulation system is highly temperature dependent. It requires adequate experience and proper understanding to interpret the dielectric response results in the presence of temperature variations and thermal instability. Proper analysis of the dielectric test result is only possible with an understanding of the physical behavior of the insulation system in response to temperature. A circuit model, which describes the dielectric behavior of the transformers main insulation system, has been investigated in this paper. The values of the parameters of the model have been identified from the dielectric tests. A correlation has been observed between the operating temperature and the equivalent model parameters that can be used as additional information for better interpretation of the dielectric test results. This paper thus reports a detailed study on the effects of temperature on dielectric measurements of a transformer under controlled laboratory conditions. Some results of practical on-site testing are also presented to demonstrate the possibility of errors that may be introduced in dielectric test results analysis unless temperature effects are taken into consideration.
引用
收藏
页码:252 / 260
页数:9
相关论文
共 25 条
[1]  
AGNEL S, 1999, P 11 INT S HIGH VOLT, V5, P116
[2]  
BOGNAR A, 1990, P CIGRE 33 SESS PAR, V2
[3]   Temperature dependant relaxation studies on oil-filled transformer [J].
Cao, HY ;
Birlasekaran, S .
CONFERENCE RECORD OF THE 2002 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2002, :174-178
[4]  
*CIGRE, 2002, DIEL RESP METH DIAGN
[5]   Effect of temperature on sensitivity of diagnostic tests on oil-impregnated paper insulation [J].
Densley, RJ ;
Gupta, BK .
ELECTRICAL INSULATION CONFERENCE AND ELECTRICAL MANUFACTURING & COIL WINDING CONFERENCE, PROCEEDINGS, 2001, :601-604
[6]   On the role of temperature and impurities in the low field conduction of insulating liquids [J].
Diabi, R ;
Filippini, JC ;
Marteau, C ;
Tobazeon, R .
ICDL 1996 - 12TH INTERNATIONAL CONFERENCE ON CONDUCTION AND BREAKDOWN IN DIELECTRIC LIQUIDS, 1996, :350-353
[7]   Moisture equilibrium in transformer paper-oil systems [J].
Du, Y ;
Zahn, M ;
Lesieutre, BC ;
Mamishev, AV ;
Lindgren, SR .
IEEE ELECTRICAL INSULATION MAGAZINE, 1999, 15 (01) :11-20
[8]  
GJAERDE AC, 1995, P 9 INT S HIGH VOLT
[9]   Dielectric response methods for diagnostics of power transformers [J].
Gubanski, SM ;
Boss, P ;
Csépes, G ;
Houhanessian, VD ;
Filippini, J ;
Guuinic, P ;
Gäfvert, U ;
Karius, V ;
Lapworth, J ;
Urbani, G ;
Werelius, P ;
Zaengl, W .
IEEE ELECTRICAL INSULATION MAGAZINE, 2003, 19 (03) :12-18
[10]  
HONGYAN C, 2002, C REC IEEE INT S EL, P174