An Identification Method for Asymmetric Faults With Line Breaks Based on Low-Voltage Side Data in Distribution Networks

被引:12
作者
Zichang, Li [1 ]
Yadong, Liu [1 ]
Yingjie, Yan [1 ]
Peng, Wang [2 ]
Xiuchen, Jiang [1 ]
机构
[1] Shanghai Jiao Tong Univ, Inst Intelligent Power Transmiss & Distribut, Shanghai 201100, Peoples R China
[2] Henan Power Supply Bur Co Ltd, Elect Power Test Inst, Luohe 462000, Henan, Peoples R China
关键词
Circuit faults; Distribution networks; Grounding; Fault diagnosis; Resistance; Monitoring; Surges; Distribution network; distribution transformer; low voltage; single-line-to-ground fault; single-line-to-ground fault with line break; two-phase short-circuit fault; two-phase fault with line break; symmetrical component method;
D O I
10.1109/TPWRD.2020.3045969
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Faults with line breaks occur more and more frequently and are difficult to detect by relay protection device in small-current grounding distribution networks. However, faults with line breaks are more likely to cause security accidents such as fires, overvoltages and electric shocks. Considering the low cost and high reliability of collecting data on the low-voltage (LV) side in distribution networks, this paper proposes a method for distinguishing between faults with line breaks and short-circuit faults on the medium-voltage (MV) side. Voltage amplitude and phase on the LV side of distribution transformer (DT) are analyzed through symmetrical component method. The amplitudes are used to identify two-phase faults with line breaks (TPFs-LBs) and two-phase short-circuit faults (TPFs-SCs); while the phases are selected to distinguish single-line-to-ground faults with line breaks (SLGFs-LBs) from single-line-to-ground faults (SLGFs). The effects of network parameters, operation conditions and external factors on the proposed method have been discussed. Simulation results verified the effectiveness of the proposed method.
引用
收藏
页码:3629 / 3639
页数:11
相关论文
共 27 条
  • [1] Al-Ghannam SH, 2017, 2017 SAUDI ARABIA SMART GRID CONFERENCE (SASG)
  • [2] [Anonymous], 2012, IEEE Standard 1366-2012
  • [3] [Anonymous], 1992, IEEE Std. 519
  • [4] [Anonymous], 2018, IEEE Standard 1547-2018, DOI DOI 10.1109/IEEESTD.2018.8332112
  • [5] [Anonymous], 1988, C571101986 IEEE
  • [6] [Anonymous], 2019, 11592019 IEEE
  • [7] Berhausen S., 2018, P INT S EL MACH ANDR, P1
  • [8] Bignucolo Fabio, 2017, CIRED - Open Access Proceedings Journal, V2017, P1414, DOI 10.1049/oap-cired.2017.0970
  • [9] Root-Cause Identification of Single Line-to-Ground Fault in Urban Small Current Grounding Systems Based on Correlation Dimension and Average Resistance
    Cong, Zihan
    Liu, Yadong
    Fang, Jian
    Wang, Peng
    Guo, Linhui
    Jiang, Xiuchen
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (04) : 1834 - 1843
  • [10] Single Line-to-Ground Faulted Line Detection of Distribution Systems With Resonant Grounding Based on Feature Fusion Framework
    Du, Ying
    Liu, Yadong
    Shao, Qingzhu
    Luo, Lingen
    Dai, Jindun
    Sheng, Gehao
    Jiang, Xiuchen
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (04) : 1766 - 1775