Investigation of SSR in Practical DFIG-Based Wind Farms Connected to a Series-Compensated Power System

被引:440
作者
Wang, Liang [1 ]
Xie, Xiaorong [2 ]
Jiang, Qirong [2 ]
Liu, Hui [3 ]
Li, Yu [3 ]
Liu, Huakun [2 ]
机构
[1] Beijing Inst Technol, Sch Automat, Beijing 100081, Peoples R China
[2] Tsinghua Univ, Dept Elect Engn, State Key Lab Power Syst, Beijing 100084, Peoples R China
[3] North China Elect Power Res Inst, Beijing 100045, Peoples R China
基金
中国国家自然科学基金;
关键词
Doubly-fed induction generator; fixed series capacitor; induction generator effect; subsynchronous control interaction; subsynchronous resonance; INDUCTION GENERATOR;
D O I
10.1109/TPWRS.2014.2365197
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Subsynchronous resonance (SSR) was observed in wind farms located in North China. These wind farms prevailingly consist of doubly-fed induction generators (DFIGs) and are connected to series-compensated transmission lines. The observed resonant frequency is about 6 similar to 8 Hz, which is much lower than that of the reported SSR occurred in Texas. The frequency varies during the occurrence and this phenomenon is observed for the first time. The output power is usually within a certain range, when SSR occurs. Based on the practical system, an equivalent simulation system has been established, in which wind farms are modeled as many identical low rating DFIGs. Then, the SSR event is reproduced by simulations. Analysis results indicate that SSR happens even when the equivalent transmission system compensation level seen from wind farms is only 6.67%. Eigenvalue analysis shows that this phenomenon is an electrical resonance, and could be affected considerably by wind speed, number and control of DFIGs. The number of in-service DFIGs has a nonlinear impact on the damping of SSR. An equivalent electric circuit is deduced to intuitively explain why SSR happens and how the above factors affect it. Considering its features, this phenomenon is recognized as DFIG control participated induction generator effect.
引用
收藏
页码:2772 / 2779
页数:8
相关论文
共 11 条
[1]  
Adams J, 2012, TRANS DISTRIB CONF
[2]  
[Anonymous], R D CHINESE STRATEGI
[3]  
[Anonymous], POWER SYSTEM STABILI
[4]  
[Anonymous], ERCOT CREZ REACT POW
[5]   Modal Analysis of a DFIG-Based Wind Farm Interfaced With a Series Compensated Network [J].
Fan, Lingling ;
Zhu, Chanxia ;
Miao, Zhixin ;
Hu, Minqiang .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2011, 26 (04) :1010-1020
[6]   Modeling of DFIG-Based Wind Farms for SSR Analysis [J].
Fan, Lingling ;
Kavasseri, Rajesh ;
Miao, Zhixin Lee ;
Zhu, Chanxia .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) :2073-2082
[7]   SUBSYNCHRONOUS RESONANCE ZONES IN IEEE BENCH MARK POWER-SYSTEM [J].
FOUAD, AA ;
KHU, KT .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1978, 97 (03) :754-762
[8]  
Irwin GD, 2011, IEEE POW ENER SOC GE
[9]   Modeling of the wind turbine with a doubly fed induction generator for grid integration studies [J].
Lei, YZ ;
Mullane, A ;
Lightbody, G ;
Yacamini, R .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2006, 21 (01) :257-264
[10]   Impedance-Model-Based SSR Analysis for Type 3 Wind Generator and Series-Compensated Network [J].
Miao, Zhixin .