Modeling and Insulation Performance Analysis of Composite Transmission Line Tower Under Lightning Overvoltage

被引:10
作者
Huangfu, Youpeng [1 ]
Wang, Shuhong [1 ]
Wang, Guolin [1 ]
Xu, Weijie [1 ]
Zhang, Haijun [1 ]
机构
[1] Xi An Jiao Tong Univ, Fac Elect Engn, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Peoples R China
基金
中国国家自然科学基金;
关键词
Composite transmission line (TL) tower; finite-element method (FEM); lightning overvoltage; multi-conductor transmission line (MTL);
D O I
10.1109/TMAG.2014.2356859
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper, a new non-uniform multiconductor transmission line model combining with lumped circuit elements for a composite transmission line (TL) tower under lightning strokes is established. The metal ground-wire cross arms, the metal tower main body and its bracings are modeled as equivalent horizontal and vertical TLs, respectively. The two grounding ladders are regarded as two parallel-vertical TLs considering their mutual coupling. These distributed TL parameters are calculated by analytic equations. The composite arms are equivalent as lumped capacitances determined by employing 3-D finite-element method. The lightning overvoltage analysis for a 330-kV composite tower is performed by applying the hybrid model. The incident and reflected voltages are calculated. The insulation performance evaluation for the composite tower is discussed in detail.
引用
收藏
页数:4
相关论文
共 10 条
[1]   TOWER MODELING FOR LIGHTNING SURGE ANALYSIS USING ELECTROMAGNETIC TRANSIENTS PROGRAM [J].
ALMEIDA, ME ;
DEBARROS, MTC .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1994, 141 (06) :637-639
[2]   FREQUENCY-DEPENDENT IMPEDANCE OF VERTICAL CONDUCTORS AND A MULTICONDUCTOR TOWER MODEL [J].
AMETANI, A ;
KASAI, Y ;
SAWADA, J ;
MOCHIZUKI, A ;
YAMADA, T .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1994, 141 (04) :339-345
[3]  
Elkins M, 2011, P IEEE PES 12 INT C, V5, P1
[4]   Nonuniform transmission tower model for lightning transient studies [J].
Gutiérrez, JAR ;
Moreno, P ;
Naredo, JL ;
Bermúdez, JL ;
Paolone, A ;
Nucci, CA ;
Rachidi, F .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (02) :490-496
[5]  
Gutierrez R J. A., 1999, IEEE Power Engineering Review, V19, P55, DOI 10.1109/39.773793
[6]   Modelling of a transmission tower for lightning-surge analysis [J].
Hara, T ;
Yamamoto, O .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1996, 143 (03) :283-289
[7]   MULTISTORY TRANSMISSION TOWER MODEL FOR LIGHTNING SURGE ANALYSIS [J].
ISHII, M ;
KAWAMURA, T ;
KOUNO, T ;
OHSAKI, E ;
SHIOKAWA, K ;
MUROTANI, K ;
HIGUCHI, T .
IEEE TRANSACTIONS ON POWER DELIVERY, 1991, 6 (03) :1327-1335
[8]  
LaForest J. J., 1987, TRANSMISSION LINE RE
[9]   TOWER SURGE IMPEDANCE [J].
SARGENT, MA ;
DARVENIZA, M .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1969, PA88 (05) :680-+
[10]   Method of Calculating the Lightning Outage Rate of Large-sized Transmission Lines [J].
Taniguchi, Sakae ;
Tsuboi, Toshihiro ;
Okabe, Shigemitsu ;
Nagaraki, Yoshimi ;
Takami, Jun ;
Ota, Hiroshi .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (04) :1276-1283