Experimental evaluation of control performance of MPC as a regulatory controller

被引:11
作者
Khan, Mohammad [1 ]
Tahiyat, Malik [2 ]
Imtiaz, Syed [1 ]
Choudhury, M. A. A. Shoukat [2 ]
Khan, Faisal [1 ]
机构
[1] Mem Univ Newfoundland, Safety & Risk Engn Grp, St John, NF, Canada
[2] Bangladesh Univ Engn & Technol, Dept Chem Engn, Dhaka, Bangladesh
基金
加拿大自然科学与工程研究理事会;
关键词
Model predictive control; PI; Control performance; CSTH; MODEL-PREDICTIVE CONTROL; PID CONTROL; IMPLEMENTATION; DESIGN;
D O I
10.1016/j.isatra.2017.04.024
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Proportional-integral-derivative (PID) control is widely practised as the base layer controller in the industry due to its robustness and design simplicity. However, a supervisory control layer over the base layer, namely a model predictive controller (MPC), is becoming increasingly popular with the advent of computer process control. The use of a supervisory layer has led to different control structures. In this study, we perform an objective investigation of several commonly used control structures such as 'Cascaded PI controller', 'DMC cascaded to PI' and 'Direct DMC'. Performance of these control structures are compared on a pilot-scale continuous stirred tank heater (CSTH) system. We used dynamic matrix control (DMC) algorithm as a representative of MPC. In the DMC cascaded to PI structure, the flow-loops are regulated by the PI controller. On top of that a DMC manipulates the set-points of the flow-loops to control the temperature and the level of water in the tank. The 'Direct DMC' structure, as its name suggests, uses DMC to manipulate the valves directly. Performance of all control structures were evaluated based on the integrated squared error (ISE) values. In this empirical study, the 'Direct DMC' structure showed a promise to act as regulatory controller. The selection of control frequency is critical for this structure. The effect of control frequency on controller performance of the 'Direct DMC' structure was also studied. (C) 2017 ISA. Published by Elsevier Ltd. All rights reserved.
引用
收藏
页码:512 / 520
页数:9
相关论文
共 23 条
[1]  
[Anonymous], 2010, PROCESS DYNAMICS CON
[2]   The future of PID control [J].
Åström, KJ ;
Hägglund, T .
CONTROL ENGINEERING PRACTICE, 2001, 9 (11) :1163-1175
[3]  
Bemporad A, 1999, LECT NOTES CONTR INF, V245, P207
[4]  
Bonivento C., 2001, P 9 MED C CONTR AUT, P6
[5]  
Desborough L., 2001, INCREASING CUSTOMER
[6]   Tuning guidelines of a dynamic matrix controller for integrating (non-self-regulating) processes [J].
Dougherty, D ;
Cooper, DJ .
INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2003, 42 (08) :1739-1752
[7]  
Ghadami M, 2013, 2013 8TH ANNUAL IEEE INTERNATIONAL CONFERENCE ON NANO/MICRO ENGINEERED AND MOLECULAR SYSTEMS (IEEE NEMS 2013), P895
[8]   Control of integrating processes using dynamic matrix control [J].
Gupta, YP .
CHEMICAL ENGINEERING RESEARCH & DESIGN, 1998, 76 (A4) :465-470
[9]   From PID to Active Disturbance Rejection Control [J].
Han, Jingqing .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2009, 56 (03) :900-906
[10]  
Khan M, 2014, ADCONIP