Influence of Lightning Flashover Criterion on the Calculated Lightning withstand Level of ±800kV UHVDC Transmission Lines at High Altitude

被引:16
|
作者
Han, Yongxia [1 ]
Tang, Li [1 ]
Li, Licheng [1 ]
He, Qiuping [1 ]
Hao, Yanpeng [1 ]
Yao, Senjing [2 ]
机构
[1] S China Univ Technol, Sch Elect Power, Guangzhou 510640, Guangdong, Peoples R China
[2] Shenzhen Power Supply Bur Ltd, Shenzhen 518000, Peoples R China
关键词
Lightning flashover criterion; lightning withstand level; +/- 800 kV UHVDC; leader propagation model; high altitude; SURGE ANALYSIS; TOWER;
D O I
10.1109/TDEI.2014.004537
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The operation experiences of power transmission lines show the lightning outage is still the main part of the total outage rate. So it is very important to calculate the lightning overvoltage across the insulators precisely and evaluate the lightning outage of the transmission lines correctly. Lightning flashover criterion of the insulator/gap is one of the most important factors that influence the precise calculation results of the lightning withstand level of transmission lines. In China, several +/- 800 kV ultra high voltage direct current (UHVDC) power transmission projects have been set up in recent years, and the altitude of the regions that the transmission lines across ranges from 0-3650 m. The paper mainly analyzed the influence of the modelling methods of insulator/gap on the lightning withstand level of +/- 800 kV UHVDC transmission lines by PSCAD/EMTDC program. The compared lightning flashover criteria of insulator/gap include the leader propagation model recommended by CIGRE, the volt/time curve recommended by IEEE and an improved leader propagation model, which is proposed based on the lightning flashover experiments of the +/- 800 kV UHVDC line insulators carried out at an altitude of 2100 m. Meanwhile, the influences of lightning current waveform and insulator structure were also considered and compared. The simulation results show that the calculated back-flashover lightning withstand level is much lower when using the improved leader propagation than that using other flashover criterions in the paper, it is lower under the 2.6/50 mu s double exponential lightning current than that under the 2.0/50 mu s Heidler function lightning current, and it is higher when using V-string than that using I-string insulator. Besides, the influences of the lightning current waveform and the insulator structure on the calculation of shielding failure lightning withstand level are little, but the flashover criterion has obvious influences on the shielding failure lightning withstand level.
引用
收藏
页码:185 / 191
页数:7
相关论文
共 43 条
  • [31] Study on Large-tonnage Live Working Tools for ±800 kV UHVDC Transmission Lines at High Altitudes
    Peng Yong
    Huang Zehua
    Chen Bo
    Lei Xinglie
    Qiu Zhonghua
    Zhang Cimeng
    2017 1ST INTERNATIONAL CONFERENCE ON ELECTRICAL MATERIALS AND POWER EQUIPMENT (ICEMPE), 2017, : 315 - 318
  • [32] Calculation Research on Influence of Adjacent Lines on Lightning Shielding Failure of ±1100 kV DC Transmission Line
    Wen X.
    Deng Y.
    Wang L.
    He H.
    Wang Y.
    Sun Z.
    Wang, Yu (wy_20002@163.com), 1600, Power System Technology Press (41): : 3420 - 3426
  • [33] Mono-pole blocking accident analysis caused by inaccurate measurement of optical CT in ±800 kV UHVDC transmission system under lightning strike
    Qian, Weirong
    Li, Wenbo
    Sha, Pengcheng
    Deng, Junbo
    Zhang, Guanjun
    Shi, Yuhang
    Yang, Dingge
    Wu, Hao
    Han, Yanhua
    ELECTRIC POWER SYSTEMS RESEARCH, 2025, 239
  • [34] DC Flashover Performance of Ice-Covered Insulator Strings Adopted in ±800kV Transmission Lines Based on Up-And-Down Method
    Yu, Xinzhe
    Zhou, Jun
    Liu, Bo
    Su, Zhiyi
    Huang, Ruiping
    2012 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2012, : 775 - 778
  • [35] Lightning protection design strategy for transmission lines of the Qinghai-Tibet railway in high altitude permafrost region
    Zhang, Bao-Ping
    He, Jin-Liang
    Kang, Peng
    Hua, Pu-Xiao
    Gaodianya Jishu/High Voltage Engineering, 2008, 34 (06): : 1095 - 1099
  • [36] Influence of Lightning Back-flashover Intruding Wave on DC Circuit Breaker in ±500 kV MMC-HVDC Transmission System
    Sima W.
    Si Y.
    Yang M.
    Yuan T.
    Xu W.
    Li H.
    Gaodianya Jishu/High Voltage Engineering, 2019, 45 (08): : 2375 - 2384
  • [37] Study on pollution flashover characteristic of insulators on 500kV AC transmission lines in high-altitude area
    Huang, Ruiping
    Zhou, Jun
    Xu, Yueneng
    JOURNAL OF ENGINEERING-JOE, 2019, (16): : 3306 - 3309
  • [38] Measurement of Corona Characteristics and Electromagnetic Environment of ±800 kV HVDC Transmission Lines under High Altitude Condition
    Zhang, Zheng
    Zeng, Rong
    Yu, Zhanqing
    PIERS 2009 MOSCOW VOLS I AND II, PROCEEDINGS, 2009, : 61 - 65
  • [40] LIGHTNING PROTECTION SYSTEM IMPROVEMENT ON EXTRA HIGH VOLTAGE 500 KV TRANSMISSION LINES IN INDONESIA USING EXTENDED MAST TERMINAL
    Zoro, Reynaldo
    Leo, Tulus
    2009 INTERNATIONAL CONFERENCE ON ELECTRICAL ENGINEERING AND INFORMATICS, VOLS 1 AND 2, 2009, : 541 - 545