Influence of Lightning Flashover Criterion on the Calculated Lightning withstand Level of ±800kV UHVDC Transmission Lines at High Altitude

被引:16
|
作者
Han, Yongxia [1 ]
Tang, Li [1 ]
Li, Licheng [1 ]
He, Qiuping [1 ]
Hao, Yanpeng [1 ]
Yao, Senjing [2 ]
机构
[1] S China Univ Technol, Sch Elect Power, Guangzhou 510640, Guangdong, Peoples R China
[2] Shenzhen Power Supply Bur Ltd, Shenzhen 518000, Peoples R China
关键词
Lightning flashover criterion; lightning withstand level; +/- 800 kV UHVDC; leader propagation model; high altitude; SURGE ANALYSIS; TOWER;
D O I
10.1109/TDEI.2014.004537
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The operation experiences of power transmission lines show the lightning outage is still the main part of the total outage rate. So it is very important to calculate the lightning overvoltage across the insulators precisely and evaluate the lightning outage of the transmission lines correctly. Lightning flashover criterion of the insulator/gap is one of the most important factors that influence the precise calculation results of the lightning withstand level of transmission lines. In China, several +/- 800 kV ultra high voltage direct current (UHVDC) power transmission projects have been set up in recent years, and the altitude of the regions that the transmission lines across ranges from 0-3650 m. The paper mainly analyzed the influence of the modelling methods of insulator/gap on the lightning withstand level of +/- 800 kV UHVDC transmission lines by PSCAD/EMTDC program. The compared lightning flashover criteria of insulator/gap include the leader propagation model recommended by CIGRE, the volt/time curve recommended by IEEE and an improved leader propagation model, which is proposed based on the lightning flashover experiments of the +/- 800 kV UHVDC line insulators carried out at an altitude of 2100 m. Meanwhile, the influences of lightning current waveform and insulator structure were also considered and compared. The simulation results show that the calculated back-flashover lightning withstand level is much lower when using the improved leader propagation than that using other flashover criterions in the paper, it is lower under the 2.6/50 mu s double exponential lightning current than that under the 2.0/50 mu s Heidler function lightning current, and it is higher when using V-string than that using I-string insulator. Besides, the influences of the lightning current waveform and the insulator structure on the calculation of shielding failure lightning withstand level are little, but the flashover criterion has obvious influences on the shielding failure lightning withstand level.
引用
收藏
页码:185 / 191
页数:7
相关论文
共 43 条
  • [21] Calculation of lightning failures rate level on 230kv transmission lines
    Al-Qahtani, BJ
    Shwehdi, MH
    OVERVOLTAGES IN POWER, ELECTRONIC, COMPUTER AND ENGINEERING, 2005, : 69 - 74
  • [22] Calculation of lightning flashovers and backflash level on 230kV transmission lines
    Al-Qahtani, BJ
    Shwehdi, MH
    Proceedings of the Eighth IASTED International Conference on Power and Energy Systems, 2005, : 90 - 95
  • [23] Calculation of Conductors' Surface Electric Field of ±800kV UHVDC Transmission Lines with Optimized Charge Simulation Method
    Hu Qin
    Shu Lichun
    Jiang Xingliang
    Xue Rong
    Yuan Qianfei
    Zhang Shikun
    ICHVE 2008: 2008 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION, 2008, : 362 - +
  • [24] Flashover pattern analysis for 275 kV double circuit transmission lines during direct lightning strikes
    Ahmed, Nasiru Yahaya
    Illias, Hazlee Azil
    Mokhlis, Hazlie
    Fahmi, Daniar
    Abdullah, Noradlina
    ELECTRIC POWER SYSTEMS RESEARCH, 2024, 228
  • [25] Research on Lightning Withstand Level of 110kV Transmission Line Installed Current Limiting Coil
    Cai, Hansheng
    Chen, Huaifei
    Jia, Lei
    Liu, Gang
    Hu, Shangmao
    Lu, Hailiang
    Wen, Xishan
    2018 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2018,
  • [26] A Parametric Study on the Critical Lightning Currents Causing Flashover to the Overhead Lines of a ±533 kV HVDC Transmission System
    Datsios, Zacharias G.
    Ioannidis, Alexios I.
    Papadopoulos, Theofilos A.
    Tsovilis, Thomas E.
    2020 20TH IEEE INTERNATIONAL CONFERENCE ON ENVIRONMENT AND ELECTRICAL ENGINEERING AND 2020 4TH IEEE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS EUROPE (EEEIC/I&CPS EUROPE), 2020,
  • [27] Back-flashover resistance level of ±800 kV/500 kV AC-DC hybrid transmission lines
    School of Electrical Engineering, Southwest Jiaotong University, Chengdu
    610031, China
    不详
    610000, China
    不详
    200122, China
    Dianli Zidonghua Shebei Electr. Power Autom. Equip., 10 (101-106 and 114):
  • [28] Back flashover's lightning performances for 500 kV AC transmission lines with quadruple-circuits on single tower
    Chai, Ya-Jing
    Zhou, Wen-Jun
    Li, Xue
    Liu, Xiao-Dong
    Su, Hong-Mei
    Shiyou Huagong Gaodeng Xuexiao Xuebao/Journal of Petrochemical Universities, 2007, 20 (03): : 74 - 77
  • [29] Over-voltage and lightning protection for 500 kV compact transmission line in high altitude area
    Zhao, Jian-Ning
    Gu, Ding-Xie
    Huo, Feng
    Cao, Jing
    Dai, Min
    Gaodianya Jishu/High Voltage Engineering, 2011, 37 (01): : 57 - 61
  • [30] Influence accretions of front of time lightning impulse on withstand voltage of real lines and stations systems of high voltage
    Mackiewicz, Marcin Maciej
    PRZEGLAD ELEKTROTECHNICZNY, 2008, 84 (10): : 272 - 275