Benefits of integrating phase-change material with solar chimney and earth-to-air heat exchanger system for passive ventilation and cooling in summer

被引:33
作者
Long, Tianhe [1 ]
Li, Wuyan [2 ]
Lv, Yifei [1 ]
Li, Yongcai [1 ]
Liu, Shuli [3 ]
Lu, Jun [1 ]
Huang, Sheng [1 ]
Zhang, Yaya [1 ]
机构
[1] Chongqing Univ, Sch Civil Engn, Chongqing 40045, Peoples R China
[2] Tsinghua Univ, Sch Architecture, Dept Bldg Sci, Beijing 100084, Peoples R China
[3] Beijing Inst Technol, Sch Mech Engn, Beijing 100081, Peoples R China
基金
中国国家自然科学基金;
关键词
Solar chimney; Earth -to -air heat exchanger; Phase-change material; Passive ventilation; Passive cooling; THERMAL PERFORMANCE; SOLIDIFICATION; MODEL; PCM;
D O I
10.1016/j.est.2022.104037
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
A solar chimney (SC) integrated with an earth-air heat exchanger (EAHE) produces a new passive system (SCEAHE) that can passively provide fresh air and cooling capacity. An inherent disadvantage of the coupled system is the mismatch of solar radiation, airflow, and internal load. To mitigate this issue and further improve the indoor thermal environment, a phase-change material (PCM)-based SCEAHE system is proposed and investigated using a validated numerical model. The thermal inertia of the SCEAHE system was improved by integrating PCM. The simulated results showed that the maximum absorber surface temperature of the SCEAHE system with PCM was 78.8 degrees C, 16.2% lower than without PCM. The PCM charging and discharging periods were approximately 9.5 h (05:30-15:00) and 14.5 h, respectively. The completely melted period lasted approximately 5 h (15:30-20:30); solidified PCM appeared from 02:00 to 7:15 with a maximum of 24% at 05:30. By integrating PCM, the SCEAHE airflow rate was increased by 50% at night, and the maximum airflow rate was reduced by 17.8% to 209.5 m3/h during the day. The EAHE outlet air temperatures varied between 24.8 and 26.5 degrees C, and between 24.4 and 27.2 degrees C for the SCEAHE with and without PCM, respectively. With the reduced outlet air temperature, the daily indoor air temperature for the SCEAHE with PCM varied between 25.1 and 28.4 degrees C; the maximum indoor air temperature was reduced by 0.8 degrees C compared with a SCEAHE without PCM, suggesting that including PCM in the SCEAHE system increases the useful cooling capacity and creates more stable indoor thermal comfort.
引用
收藏
页数:16
相关论文
共 33 条
[1]   Solar chimneys: simulation and experiment [J].
Afonso, C ;
Oliveira, A .
ENERGY AND BUILDINGS, 2000, 32 (01) :71-79
[2]  
Bergman T.L., 2017, Fundamental of heat and mass transfer, V8th
[3]   Design evaluation of Earth-Air Heat Exchangers with multiple ducts [J].
Brum, Ruth S. ;
Ramalho, Jairo V. A. ;
Rodrigues, Michel K. ;
Rocha, Luiz A. O. ;
Isoldi, Liercio A. ;
Dos Santos, Elizaldo D. .
RENEWABLE ENERGY, 2019, 135 :1371-1385
[4]  
China Building Energy Association, 2020, CHIN BUILD EN RES RE
[5]   Experimental analysis of a PCM integrated solar chimney under laboratory conditions [J].
Dordelly, Jose Carlos Frutos ;
El Mankibi, Mohamed ;
Roccamena, Letizia ;
Remiona, Gabriel ;
Landa, Jesus Arce .
SOLAR ENERGY, 2019, 188 :1332-1348
[6]  
Garslaw H.S., 1959, CONDUCTION HEAT SOLI
[7]  
Gerhart P.M., 1992, FUNDAMENTALS FLUID M
[8]   AN EFFICIENT ALGORITHM FOR FINITE-ELEMENT SOLUTION TO TWO-DIMENSIONAL HEAT-TRANSFER WITH MELTING AND FREEZING [J].
HSIAO, JS ;
CHUNG, BTF .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1986, 108 (02) :462-464
[9]   Mathematical modelling of solidification and melting: A review [J].
Hu, H ;
Argyropoulos, SA .
MODELLING AND SIMULATION IN MATERIALS SCIENCE AND ENGINEERING, 1996, 4 (04) :371-396
[10]   Experimental study on the influence of PCM container height on heat transfer characteristics under constant heat flux condition [J].
Huang, Sheng ;
Lu, Jun ;
Li, Yongcai ;
Xie, Ling ;
Yang, Lulu ;
Cheng, Yong ;
Chen, Sukun ;
Zeng, Liyue ;
Li, Wuyan ;
Zhang, Yaya ;
Wang, Linfeng .
APPLIED THERMAL ENGINEERING, 2020, 172