Evaluation of grounding schemes used for maintenance of overhead distribution lines

被引:2
作者
Lee, CH [1 ]
Hsu, TC
机构
[1] Natl Yunlin Univ Sci & Technol, Dept Elect Engn, Touliu, Yunlin, Taiwan
[2] Tainan Off Taiwan Power Co, Tainan, Taiwan
关键词
electric shocks; re-energization; temporary grounding conductor; touch voltage;
D O I
10.1109/TPWRD.2005.848450
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper evaluates seven basic grounding schemes used for maintenance of overhead de-energized distribution lines in the system of Taiwan Power Company. The test results are summarized to determine the effective grounding scheme of protecting workers on de-energized overhead distribution lines from the source-side due to an accidental energization. The fault currents were recorded with various grounding configurations. As a result, two of grounding configurations are considered lethal.
引用
收藏
页码:2211 / 2218
页数:8