Adjustable performance analysis of combined cooling heating and power system integrated with ground source heat pump

被引:50
作者
Wang, Jiangjiang [1 ]
Chen, Yuzhu [1 ]
Dou, Chao [1 ]
Gao, Yuefen [1 ]
Zhao, Zheng [2 ]
机构
[1] North China Elect Power Univ, Sch Energy Power & Mech Engn, Baoding 071003, Hebei, Peoples R China
[2] North China Elect Power Univ, Sch Control & Comp Engn, Baoding 071003, Hebei, Peoples R China
基金
中国国家自然科学基金;
关键词
Combined cooling heating and power system; Ground source heat pump; Primary energy ratio; Exergy efficiency; Adjustable area; EXERGY ANALYSIS; CCHP SYSTEM; ADSORPTION CHILLER; ECONOMIC-ANALYSIS; OPTIMAL-DESIGN; ENERGY; BIOMASS; OPTIMIZATION;
D O I
10.1016/j.energy.2018.08.143
中图分类号
O414.1 [热力学];
学科分类号
摘要
The difference in the electricity to cooling/heating ratio between a building and combined cooling, heating, and power (CCHP) system has a significant influence on the system configuration and performance. This paper designs a CCHP system coupled with a ground source heat pump (GSHP) to coordinate the match between system supplies and building demands. The energy flows in the cooling and heating work conditions are analyzed, and the thermodynamic models of components constructed. By means of a case study, the performances of the coupling CCHP system, under design and off-design working conditions, are evaluated and analyzed using energetic indicators, including the primary energy ratio and exergy efficiency, respectively. The adjustable areas expressed by electricity and cooling/heating, as well as the adjustable performance distributions, are obtained and discussed in order to guide operation regulation of the CCHP system integrated with the GSHP. Comparisons between the CCHP system with and without GSHP indicate that the coupling CCHP system in the specific case study can save averagely 40.6% and 39.5% of the primary energy in cooling and heating work conditions, respectively. (C) 2018 Elsevier Ltd. All rights reserved.
引用
收藏
页码:475 / 489
页数:15
相关论文
共 38 条
[1]   Temperature distributions in pavement and bridge slabs heated by using vertical ground-source heat pump systems [J].
Balbay, Asim ;
Esen, Mehmet .
ACTA SCIENTIARUM-TECHNOLOGY, 2013, 35 (04) :677-685
[2]  
Balbay A, 2010, SCI RES ESSAYS, V5, P3955
[3]   Modelling and experimental investigation of an adsorption chiller using low-temperature heat from cogeneration [J].
Chorowski, Maciej ;
Pyrka, Piotr .
ENERGY, 2015, 92 :221-229
[4]   Performance Analysis of Heating Supply from a Coupled CCHP system with Ground Source Heat Pump [J].
Dou, Chao ;
Wang, Jiangjiang .
10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 :381-388
[5]   Predicting performance of a ground-source heat pump system using fuzzy weighted pre-processing-based ANFIS [J].
Esen, Hikmet ;
Inalli, Mustafa ;
Sengur, Abdulkadir ;
Esen, Mehmet .
BUILDING AND ENVIRONMENT, 2008, 43 (12) :2178-2187
[6]   Energy and exergy analysis of a ground-coupled heat pump system with two horizontal ground heat exchangers [J].
Esen, Hikmet ;
Inalli, Mustafa ;
Esen, Mehmet ;
Pihtili, Kazim .
BUILDING AND ENVIRONMENT, 2007, 42 (10) :3606-3615
[7]   Modelling and experimental performance analysis of solar-assisted ground source heat pump system [J].
Esen, Hikmet ;
Esen, Mehmet ;
Ozsolak, Onur .
JOURNAL OF EXPERIMENTAL & THEORETICAL ARTIFICIAL INTELLIGENCE, 2017, 29 (01) :1-17
[8]   Experimental evaluation of using various renewable energy sources for heating a greenhouse [J].
Esen, Mehmet ;
Yuksel, Tahsin .
ENERGY AND BUILDINGS, 2013, 65 :340-351
[9]   Cooling tests, numerical modeling and economic analysis of semi-open loop ground source heat pump system [J].
Farabi-Asl, Hadi ;
Fujii, Hikari ;
Kosukegawa, Hiroyuki .
GEOTHERMICS, 2018, 71 :34-45
[10]   Performance Analysis of CCHP System for University Campus in North China [J].
Jiang, Jinming ;
Gao, Weijun ;
Gao, Yanna ;
Wei, Xindong ;
Kuroki, Soichiro .
URBAN PLANNING AND ARCHITECTURAL DESIGN FOR SUSTAINABLE DEVELOPMENT (UPADSD), 2016, 216 :361-372