Low-temperature baseboard heaters with integrated air supply - An analytical and numerical investigation

被引:38
作者
Ploskic, Adnan [1 ]
Holmberg, Sture [1 ]
机构
[1] KTH, Sch Architecture & Built Environm, SE-13640 Stockholm, Sweden
关键词
Baseboard (skirting) heating; Low-temperature hydronic heating; Forced convective heat transfer; Channel airflow; Thermal comfort; CFD; SURFACES; DRAFT; ROOM; FLOW;
D O I
10.1016/j.buildenv.2010.07.011
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The functioning of a hydronic baseboard heating system with integrated air supply was analyzed. The aim was to investigate thermal performance of the system when cold outdoor (ventilation) airflow was forced through the baseboard heater. The performance of the system was evaluated for different ventilation rates at typical outdoor temperatures during the Swedish winter season. Three different analytical models and Computational Fluid Dynamics (CFD) were used to predict the temperature rise of the airflow inside the baseboard heater. Good agreement between numerical (CFD) and analytical calculations was obtained. Calculations showed that it was fully possible to pre-heat the incoming airflow to the indoor temperature and to cover transmission losses, using 45 degrees C supply water flow. The analytical calculations also showed that the airflow per supply opening in the baseboard heater needed to be limited to 7.0 l/s due to pressure losses inside the channel. At this ventilation rate, the integrated system with one air supply gave about 2.1 more heat output than a conventional baseboard heating system. CFD simulations also showed that the integrated system was capable of countering downdraught created by 2.0 m high glazed areas and a cold outdoor environment. Draught discomfort in the case with the conventional system was slightly above the recommended upper limit, but heat distribution across whole analyzed office space was uniform for both heating systems. It was concluded that low-temperature baseboard heating systems with integrated air supply can meet both international comfort requirements, and lead to energy savings in cold climates. (C) 2010 Elsevier Ltd. All rights reserved.
引用
收藏
页码:176 / 186
页数:11
相关论文
共 30 条
[1]  
Alvarez H., 2003, ENERGITEKNIK, P360
[2]  
ASHRAE, 1992, 551992 ASHRAE
[3]   Calculation of convective heat transfer coefficients of room surfaces for natural convection [J].
Awbi, HB .
ENERGY AND BUILDINGS, 1998, 28 (02) :219-227
[4]  
CENGEL VA, 2002, FLUID MECH FUNDAMENT, P49
[5]  
DITTUS F.W., 1930, Univ. California, V2, P443, DOI DOI 10.1016/0735-1933(85)90003-X
[6]  
EKBERG L, 2006, BFS, P38
[7]  
ELINUALIM AA, 2003, J VENTILATION, V3, P213
[8]   AIR TURBULENCE AND SENSATION OF DRAFT [J].
FANGER, PO ;
MELIKOV, AK ;
HANZAWA, H ;
RING, J .
ENERGY AND BUILDINGS, 1988, 12 (01) :21-39
[9]   NUMERICAL-SIMULATION OF THE INDOOR ENVIRONMENT [J].
GAN, GH ;
AWBI, HB .
BUILDING AND ENVIRONMENT, 1994, 29 (04) :449-459
[10]  
GNIELINSKI V, 1976, INT CHEM ENG, V16, P359