A Study of Voltage Withstand of Various Gases under AC Voltage

被引:0
作者
Tiamkatok, W. [1 ]
Chotigo, S. [1 ]
机构
[1] King Mongkuts Univ Technol Thonburi, Fac Engn, Dept Elect Engn, Bangkok 10140, Thailand
来源
PROCEEDINGS OF 2011 INTERNATIONAL CONFERENCE ON ELECTRICAL INSULATING MATERIALS (ISEIM) | 2011年
关键词
Characteristic; Breakdown voltage; Gases; Insulation; Dielectric Strengths;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
At present, equipments in Gas Insulated Substation(GIS) such as circuit breaker, ground switch, busbar and transformer use SF6 as its insulation because of its better electrical withstand, less area for installation and arc quenching for circuit breaker. However, SF6 has high cost. Furthermore, it causes green house effect and poisonous environment. In this research, the voltage withstand of Ar, He, O-2, CO2, Air, and N-2 was studied to compare with that of SF6. The voltage withstand of each gas under 50 Hz AC voltage was studied using a chamber designed following ASTM D 2477-96 which consists of rod-plane and sphere-plane gap made of stainless steel. Gap distances in this experiment were 5, 10, 15 and 20 mm while the gas pressures were varied to 1, 2 and 3 bars. The results show that He has the lowest voltage withstand compared to other gases at the same gap distance and pressure.
引用
收藏
页码:425 / 428
页数:4
相关论文
共 4 条
[1]  
[Anonymous], 1989, 247796 ASTMD
[2]  
Clavreul R., 1996, Seventh International Conference on Dielectric Materials, Measurements and Applications (Conf. Publ. No.430), P176, DOI 10.1049/cp:19961016
[3]  
Graf R., 2000, 2000 C EL INS DIEL P
[4]   SF6 breakdown in GIS [J].
Tekletsadik, K ;
Campbell, LC .
IEE PROCEEDINGS-SCIENCE MEASUREMENT AND TECHNOLOGY, 1996, 143 (05) :270-276