Flashover performance of HVDC iced insulator strings

被引:27
|
作者
Li, Peng [1 ]
Fan, Jianbin [1 ]
Li, Wufeng [1 ]
Su, Zhiyi [1 ]
Zhou, Jun [1 ]
机构
[1] China Elect Power Res Inst, Beijing 100085, Peoples R China
关键词
iced insulator string; dc flashover; flashover; overhead line;
D O I
10.1109/TDEI.2007.4401215
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Based on artificial icing test results, it was found that the dc flashover voltage of iced insulator strings was non-linear with different string lengths. An experimental formula of flashover voltage on iced insulators of different string lengths is introduced in this paper. Icing tests were carried out on different kinds of insulators including DC anti-fog, double-shed and three-shed insulators. Under serious ice conditions, the DC flashover voltages of the different types of insulator strings were very close. The flashover voltage of energized iced strings was a little higher than that of de-energized ones.
引用
收藏
页码:1334 / 1338
页数:5
相关论文
共 50 条
  • [41] Voltage sag due to pollution induced flashover across ceramic insulator strings
    Subba Reddy B.
    Goswami A.K.
    International Journal of Emerging Electric Power Systems, 2017, 18 (06)
  • [42] Effect of inverted T arrangement on AC pollution flashover characteristics of insulator strings
    Jiang, Xingliang
    Ren, Xiaodong
    Wang, Han
    Han, Xingbo
    Bi, Conglai
    Li, Zhiyu
    Hou, Ledong
    HIGH VOLTAGE, 2019, 4 (02) : 97 - 104
  • [43] Flashover Prevention on High-altitude HVAC Transmission Line Insulator Strings
    Huang, Daochun
    Ruan, Jiangjun
    Cai, Wei
    Li, Tianwei
    Wei, Yuanhang
    Liu, Jia
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2009, 16 (01) : 88 - 98
  • [44] Pollution Flashover Characteristics of Insulator Strings with Inverted T-type Arrangement
    Jiang X.
    Wang H.
    Yang Z.
    Han X.
    Wu H.
    Gaodianya Jishu/High Voltage Engineering, 2019, 45 (03): : 701 - 707
  • [45] Behavior comparison of corona inception and flashover voltage between HVAC and HVDC insulator
    Karn, A.
    Potivejkul, S.
    Pattanadech, N.
    Yutthagowith, P.
    IPEC: 2005 International Power Engineering Conference, Vols 1 and 2, 2005, : 334 - 338
  • [46] Resistance measurements and interpretations relating to flashover of artificially contaminated ceramic insulator strings
    Reddy, BS
    Nagabhushana, GR
    PLASMA SCIENCE & TECHNOLOGY, 2003, 5 (06) : 2093 - 2100
  • [47] FLASHOVER TESTS OF ARTIFICIALLY ICED INSULATORS
    CHARNESKI, MD
    GAIBROIS, GL
    WHITNEY, BF
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (08): : 2429 - 2433
  • [48] A STUDY ON THE PROFILE OF HVDC INSULATORS - DC FLASHOVER PERFORMANCE
    FAZELIAN, M
    WU, CY
    CHENG, TC
    NOUR, HI
    WANG, LJ
    IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1989, 24 (01): : 119 - 125
  • [49] A survey of the flashover performance of HVDC converter station insulators
    Almgren, B
    Åström, U
    Wu, D
    POWERCON '98: 1998 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY - PROCEEDINGS, VOLS 1 AND 2, 1998, : 516 - 519
  • [50] ON THE ORIGIN, SIGNIFICANCE, AND MINIMIZATION OF NONUNIFORM CONTAMINATION ALONG HVDC INSULATOR STRINGS
    OLSEN, RG
    DAFFE, J
    SARKINEN, CF
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1981, 100 (03): : 971 - 980