Flashover performance of HVDC iced insulator strings

被引:27
|
作者
Li, Peng [1 ]
Fan, Jianbin [1 ]
Li, Wufeng [1 ]
Su, Zhiyi [1 ]
Zhou, Jun [1 ]
机构
[1] China Elect Power Res Inst, Beijing 100085, Peoples R China
关键词
iced insulator string; dc flashover; flashover; overhead line;
D O I
10.1109/TDEI.2007.4401215
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Based on artificial icing test results, it was found that the dc flashover voltage of iced insulator strings was non-linear with different string lengths. An experimental formula of flashover voltage on iced insulators of different string lengths is introduced in this paper. Icing tests were carried out on different kinds of insulators including DC anti-fog, double-shed and three-shed insulators. Under serious ice conditions, the DC flashover voltages of the different types of insulator strings were very close. The flashover voltage of energized iced strings was a little higher than that of de-energized ones.
引用
收藏
页码:1334 / 1338
页数:5
相关论文
共 50 条
  • [2] AN, RI AND TVI FROM SINGLE UNIT FLASHOVER OF HVDC SUSPENSION INSULATOR STRINGS
    FUKUSHIMA, M
    SUNAGA, Y
    SASANO, T
    SAWADA, Y
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1977, 96 (04): : 1233 - 1241
  • [3] Influence of length and arrangement of iced insulator strings on DC flashover voltage at high altitude districts
    State Key Laboratory of Power Transmission Equipment and System Security and New Technology, Chongqing University, Chongqing 400030, China
    Zhongguo Dianji Gongcheng Xuebao, 2008, 3 (1-5):
  • [4] Effect of test methods on AC flashover performance of iced porcelain insulator string
    Jiang, Xing-Liang
    Jiang, Yi-Ping
    Hu, Jian-Lin
    Zhang, Zhi-Jin
    Gaodianya Jishu/High Voltage Engineering, 2009, 35 (08): : 1869 - 1873
  • [5] Equivalence of pollution simulation methods for AC flashover performance of iced composite insulator
    Jiang, Xing-Liang
    Zhang, Zhi-Jin
    Hu, Jian-Lin
    Yang, Jian-Lan
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2010, 30 (13): : 115 - 120
  • [6] Effect of Hydrophobicity Coating on Insulator Icing and DC Flashover Performance of Iced Insulators
    Jiang, Xingliang
    Ma, Jun
    Zhang, Zhijing
    Hu, Jianlin
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (02) : 351 - 359
  • [7] DC Flashover Characteristics of the Iced-Covered Inverted T-Type Insulator Strings with Different Configuration
    Huang Y.
    Jiang X.
    Yang G.
    Zhu M.
    Chen Y.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2021, 36 (24): : 5294 - 5303
  • [8] AC flashover performance and mechanism of polluted and iced IEC standard suspension insulator string
    Sun, CX
    Jiang, XL
    Shu, LC
    Lu, Z
    Chen, MY
    PROCEEDINGS OF THE THIRTEENTH (2003) INTERNATIONAL OFFSHORE AND POLAR ENGINEERING CONFERENCE, VOL 1, 2003, : 409 - 415
  • [9] Flashover Performance and Process of Suspension Insulator Strings Artificially Covered with Snow
    Hu, Yuyao
    Guo, Sihua
    Xian, Richang
    Han, Xingbo
    Yang, Zhongyi
    Wu, Ying
    ENERGIES, 2018, 11 (11)
  • [10] Recurrent Plot Analysis of Leakage Current on Flashover Performance of Rime-iced Composite Insulator
    Liu, Yong
    Du, B. X.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (02) : 465 - 472