Effects of hot SF6 on post-arc circuit breaker design

被引:26
作者
Uchii, T [1 ]
Nishiwaki, S
Boggs, S
机构
[1] TM T&D Corp, Kawasaki, Kanagawa 2100862, Japan
[2] Univ Toronto, Dept Elect & Comp Engn, Toronto, ON, Canada
[3] Univ Connecticut, Dept Elect Engn, Elect Insulat Res Ctr, Storrs, CT 06269 USA
[4] Univ Connecticut, Dept Phys, Elect Insulat Res Ctr, Storrs, CT 06269 USA
关键词
Arc; gas circuit breaker; SF6; transient recovery voltage;
D O I
10.1109/TPWRD.2003.820210
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
SF6 is blown through the arc during interruption of an SF6 puffer circuit breaker. This hot gas flows down an exhaust tube into the chamber of a dead tank circuit breaker where it can lower the dielectric withstand between the exhaust tube and the tank of the circuit breaker, leading to dielectric breakdown during the transient recovery voltage after clearing. This paper presents experimental evidence that any such breakdown is controlled by,the hot gas near the exhaust tube, with cold gas in the remainder of gap having little effect on the breakdown voltage. This experimental conclusion is supported by a detailed theory for conditions under which breakdown can occur.
引用
收藏
页码:124 / 130
页数:7
相关论文
共 10 条
[1]   Analytical approach to SF6 breakdown under transient conditions [J].
Boggs, S ;
Uchii, T ;
Nishiwaki, S .
IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (03) :751-757
[2]   The influence of the presence of tungsten of SF6 arc plasmas [J].
Chervy, B .
JOURNAL OF PHYSICS D-APPLIED PHYSICS, 1996, 29 (08) :2156-2161
[3]   Calculation of the uniform breakdown field strength of SF6 gas [J].
Cliteur, GJ ;
Hayashi, Y ;
Haginomori, E ;
Suzuki, K .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1998, 5 (06) :843-849
[4]   COMPOSITION AND TRANSPORT PROPERTIES OF SE6 AND THEIR USE IN A SIMPLIFIED ENTHALPY FLOW ARC MODEL [J].
FROST, LS ;
LIEBERMA.RW .
PROCEEDINGS OF THE INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS, 1971, 59 (04) :474-&
[5]   On the hot gas exhaustion in the exhaust chamber of a gas circuit breaker after short-circuit current interruption [J].
Hayashi, Y ;
Suzuki, K ;
Haginomori, E ;
Toda, H ;
Ikeda, H .
JOURNAL OF PHYSICS D-APPLIED PHYSICS, 1997, 30 (22) :3123-3130
[6]  
JIANG G, 1999, P ANN REP IEEE C EL, P609
[7]   BREAKDOWN EXPERIMENTS IN DILUTED SF6 AT ELEVATED-TEMPERATURES [J].
ROTHHARDT, L ;
MASTOVSKY, J ;
BLAHA, J .
JOURNAL OF PHYSICS D-APPLIED PHYSICS, 1985, 18 (10) :L155-L157
[8]  
SAKUTA T, 1992, 10TH INT C GAS DISCH, V1, P110
[9]  
UCHII T, 1999, I EL ENG JPN HIGH VO
[10]   INHOMOGENEOUS FIELD BREAKDOWN IN GIS - THE PREDICTION OF BREAKDOWN PROBABILITIES AND VOLTAGES .1. OVERVIEW OF A THEORY FOR INHOMOGENEOUS FIELD BREAKDOWN IN SF6 [J].
WIEGART, N ;
NIEMEYER, L ;
PINNEKAMP, F ;
BOECK, W ;
KINDERSBERGER, J ;
MORROW, R ;
ZAENGL, W ;
ZWICKY, M ;
GALLIMBERTI, I ;
BOGGS, SA .
IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (03) :923-930