Experimental Investigations on Evaporative Condensers Performance

被引:13
作者
Fiorentino, Maria [1 ]
Starace, Giuseppe [2 ]
机构
[1] Decsa Srl, Via Cappelletta, I-27058 Voghera, Italy
[2] Univ Salento, Dept Engn Innovat, Via Monteroni, I-73100 Lecce, Italy
来源
BEYOND NZEB BUILDINGS | 2017年 / 140卷
关键词
thermofluid dynamic analysis; evaporative condensers; refrigeration plants; heat rejection; experimental tests; COMPREHENSIVE DESIGN; COOLERS;
D O I
10.1016/j.egypro.2017.11.157
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The evaporative condensers operate at lower condensing temperatures compared with dry heat transfer units when connected to the same refrigeration system, as well as involve less water and reduce the pumping power associated to cooling towers. These characteristics are strictly correlated with the evaporation process. For these reasons they are conveniently used for heat rejection in big industrial plants and recent technological developments have made it possible to exploit their higher efficiency even in smaller air conditioning systems. In this work a test rig for the evaporative condensers performance analysis and the relevant experimental activities are presented. The combined effect of the dry bulb temperature and relative humidity on the system performance has been investigated. The maximum reduction of the heat transfer rate, due to an increase of 6 % of the initial value of relative humidity, results of 30 % for the highest dry bulb temperature. The air processes plot in a psychometric chart show that the latent to sensible heat transfer ratio decreases with relative humidity. (C) 2017 The Authors. Published by Elsevier Ltd.
引用
收藏
页码:458 / 466
页数:9
相关论文
共 16 条
[1]   Consolidated experimental heat and mass transfer database for a reduced scale evaporative condenser [J].
Acunha Junior, Ivoni Carlos ;
Smith-Schneider, Paulo .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2016, 66 :21-31
[2]  
Erens J, 1988, 25 NAT HEAT TRANSF C, V84, P140
[3]   Performance of evaporative condensers [J].
Ettouney, HM ;
El-Dessouky, HT ;
Bouhamra, W ;
Al-Azmi, B .
HEAT TRANSFER ENGINEERING, 2001, 22 (04) :41-55
[4]   Numerical and Experimental Performance Analysis of Evaporative Condensers [J].
Fiorentino, Maria ;
Starace, Giuseppe .
71ST CONFERENCE OF THE ITALIAN THERMAL MACHINES ENGINEERING ASSOCIATION (ATI 2016), 2016, 101 :26-33
[5]   Experimental and numerical study of an evaporatively-cooled condenser of air-conditioning systems [J].
Islam, M. R. ;
Jahangeer, K. A. ;
Chua, K. J. .
ENERGY, 2015, 87 :390-399
[6]   Numerical investigation of transfer coefficients of an evaporatively-cooled condenser [J].
Jahangeer, K. A. ;
Tay, Andrew A. O. ;
Islam, Md. Raisul .
APPLIED THERMAL ENGINEERING, 2011, 31 (10) :1655-1663
[7]  
Kreid D. K., 1978, APPROXIMATE ANAL HEA
[8]  
Leidenfrost W., 1982, Heat Transfer Engineering, V3, P38
[9]  
MIZUSHIMA T, 1967, INT CHEM ENG, V7, P727
[10]  
Parker R.O., 1961, CHEM ENG PROG, V57, P138