Changes in mechanical properties of impregnated Nomex papers 410 and 910 during accelerated aging

被引:32
作者
Arroyo-Fernandez, Oscar H. [1 ,2 ]
Jalbert, Jocelyn [1 ]
Rodriguez-Celis, Esperanza M. [1 ]
Duchesne, Steve [1 ]
Morin, Brigitte [1 ]
Fofana, Issouf [2 ]
机构
[1] Inst Rech Hydroquebec IREQ, 1800 Blvd Lionel Boulet, Varennes, PQ J3X 1S1, Canada
[2] UQAC, Res Chair Aging Power Network Infrastruct ViAHT, 555 Blvd Univ, Chicoutimi, PQ G7H 2B1, Canada
关键词
Nomex; 410; 910; Aramid; Cellulosic insulation; Power transformer; Solid insulation; CHAIN-END GROUPS; POWER TRANSFORMERS; TENSILE-STRENGTH; CELLULOSE; INSULATION; METHANOL; KINETICS; DEPOLYMERIZATION; TEMPERATURE; PERFORMANCE;
D O I
10.1016/j.polymertesting.2020.106358
中图分类号
TB3 [工程材料学];
学科分类号
0805 ; 080502 ;
摘要
New materials are currently being developed for applications in transformer design. With the useful life of transformers now determined by solid insulation conditions, a better understanding of aging kinetics is important in order to improve electrical system management and planning from the technical and economic points of view. This paper summarizes an investigation of the effects of impregnating aramid and cellulose/aramid papers (Nomex 410 and 910) with insulation fluids (Nynas Polaris and Luminol Tri) at thermally accelerated conditions (170 degrees C) on their mechanical properties. It was found that Nomex 410 (100% aramid) showed only a small change in tensile strength (similar to 5% decrease) after accelerated aging (around 7500 h). However, its elongation capacity was significantly reduced (similar to 45-70% decrease for dry and wet Nomex 410, respectively) by the end of the aging process, probably due to hydrolysis. In addition, the interaction between water and aramid hydrogen bonds at high temperatures produced the rupture and then, the randomly rebuilt of these bonds in meta-aramid fibres, thereby reducing its plastic deformation capacity. In the case of Nomex 910 (aramid enhanced cellulose), its mechanical properties were maintained for a longer time than those of thermally upgraded Kraft paper (TUK), as measured by the retained percentage of tensile index. However, when the tensile index was used instead of the retained percentage, TUK showed a higher tensile index value than Nomex 910 during the initial stage, while the values for both papers became similar during the second stage. It is only at the end of the aging process that Nomex 910 presented an advantage over TUK paper due to the addition of the aramid fibres. It was also found that the inception fractures in Nomex 910, as a fibrous layered composite paper, start in the weakest part of the composite, probably in the central cellulose layer. The fracture line follows the weakest path, avoiding the aramid fibres. The results presented in this paper can be used as a benchmark for improving our understanding of aging and changes in the mechanical properties of these relatively new materials used in the solid insulation of power transformers. A better understanding of the aging characteristics (thermal degradation) of aramid-based papers should help better assess the condition of the new generation of power transformer fleets.
引用
收藏
页数:13
相关论文
共 31 条
[1]  
Abdin Y, 2015, Fatigue of textile composites, P85, DOI [10.1016/B978-1-78242-281-5.00005-5, DOI 10.1016/B978-1-78242-281-5.00005-5]
[2]   Temperature dependence of methanol and the tensile strength of insulation paper: kinetics of the changes of mechanical properties during ageing [J].
Arroyo, Oscar H. ;
Jalbert, Jocelyn ;
Fofana, Issouf ;
Ryadi, Mohamed .
CELLULOSE, 2017, 24 (02) :1031-1039
[3]   Relationships between Methanol Marker and Mechanical Performance of Electrical Insulation Papers for Power Transformers under Accelerated Thermal Aging [J].
Arroyo, Oscar H. ;
Fofana, Issouf ;
Jalbert, Jocelyn ;
Ryadi, Mohamed .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (06) :3625-3632
[4]   Assessing Changes in Thermally Upgraded Papers with Different Nitrogen Contents under Accelerated Aging [J].
Arroyo-Fernandez, Oscar H. ;
Fofana, Issouf ;
Jalbert, Jocelyn ;
Rodriguez, Esperanza ;
Rodriguez, Lidia B. ;
Ryadi, Mohamed .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (03) :1829-1839
[5]  
Ash RA, 2016, WOODH PUB S COMPOS S, V71, P285, DOI 10.1016/B978-0-08-100406-7.00009-X
[6]  
Campbell F.C., 2004, Manufacturing Processes for Advanced Composites, P39, DOI 10.1016/B978-185617415-2/50003-4
[7]  
DEOPURA B.L., 2015, TEXT FASH, V5, P97
[8]   Significance and Detection of Very Low Degree of Polymerization of Paper in Transformers [J].
Duval, Michel ;
de Pablo, Alfonso ;
Atanasova-Hoehlein, Ivanka ;
Grisaru, Marius .
IEEE ELECTRICAL INSULATION MAGAZINE, 2017, 33 (01) :31-38
[9]   Degradation of cellulosic insulation in power transformers. Part 4: Effects of ageing on the tensile strength of paper [J].
Emsley, AM ;
Heywood, RJ ;
Ali, M ;
Xiao, X .
IEE PROCEEDINGS-SCIENCE MEASUREMENT AND TECHNOLOGY, 2000, 147 (06) :285-290
[10]  
Fernandez O.H. Arroyo, 2017, THESIS