Improving reverse cycle defrosting performance of air source heat pumps using thermal storage-based refrigerant sub-cooling energy

被引:31
作者
Dong Jiankai [1 ]
Jiang Yiqiang [1 ]
Deng Shiming [2 ]
Yao Yang [1 ]
Qu Minglu [2 ]
机构
[1] Harbin Inst Technol, Dept Bldg Thermal Energy Engn, Harbin 150006, Heilongjiang, Peoples R China
[2] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Kowloon, Hong Kong, Peoples R China
关键词
POSSIBLE ADVANTAGE; EXCHANGER; SIMULATION; SYSTEM; MODEL;
D O I
10.1177/0143624411406016
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
When an air source heat pump (ASHP) unit is used for space heating at a low ambient temperature in winter, frost may be formed on its outdoor coil surface. Over time, frost accumulation on coil surface may become sufficient to restrict air passage through the coil and increase the heat transfer resistance between ambient air and coil surface, leading to performance degradation for the outdoor coil, or even the shutdown of the ASHP unit. Therefore, periodic defrosting is necessary. Currently, the most widely used standard defrosting method for an ASHP unit is reverse cycle defrosting. During a standard reverse cycle defrosting (SRCD) operation, the indoor coil in an ASHP unit actually acts as an evaporator. Because the indoor fan is usually turned off during defrosting, there is an insignificant amount of energy from indoor coil, leading to a number of associated operational problems such as a longer defrosting duration and the risk of having a lower air temperature inside a heated space during defrosting, etc. To solve the fundamental problem of insufficient heat available during defrosting while ensuring the efficient and safe system operation, a novel reverse cycle defrosting (NRCD) method which is thermal energy storage-based using sub-cooling energy of refrigerant for ASHPs has been developed. Comparative experiments using both the SRCD method and the NRCD method were carried out on an experimental ASHP unit with a nominal 2.5kW heating capacity. Experimental results clearly suggested that when using the NRCD method, the discharge and suction pressures were increased by 0.56 and 0.12 MPa, respectively. Furthermore, the defrosting duration and heating-resumption duration were shortened by 30.8% and 25.0%, respectively, and the defrosting energy consumption was reduced by 13.9%, compared to those when using the SRCD method. Practical application: ASHPs have been widely used worldwide due to their significant energy-saving potentials. However, frost can be formed on the outdoor coil surface when an ASHP unit operates for space heating. Frost accumulation on coil surface reduces the coil's efficiency, or causes even the shutdown of the ASHP unit. Reverse cycle defrosting is the most widely used standard defrosting method. This paper presents the reverse cycle defrosting performance for an ASHP unit with a PCM-HE acting as both a sub-cooler during heating operation and a heat source during defrosting operation, which could help to ensure the safe operation and achieve a higher defrosting efficiency of the ASHP unit.
引用
收藏
页码:223 / 236
页数:14
相关论文
共 23 条
[1]   A criterion for predicting the possible advantage of adopting a suction/liquid heat exchanger in refrigerating system [J].
Aprea, C ;
Ascani, M ;
de Rossi, F .
APPLIED THERMAL ENGINEERING, 1999, 19 (04) :329-336
[2]   The application of photo-coupler for frost detecting in an air-source heat pump [J].
Byun, JS ;
Jeon, CD ;
Jung, JH ;
Lee, J .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2006, 29 (02) :191-198
[3]   Frost retardation of an air-source heat pump by the hot gas bypass method [J].
Byun, Ju-Suk ;
Lee, Jinho ;
Jeon, Chang-Duk .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (02) :328-334
[4]   Experiment investigation of reverse cycle defrosting methods on air source heat pump with TXV as the throttle regulator [J].
Ding, YJ ;
Ma, GY ;
Chai, QH ;
Yi, JA .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2004, 27 (06) :671-678
[5]   Performance enhancement of a heat pump system with ice storage subcooler [J].
Hsiao, Ming-Jer ;
Kuo, Yu-Fu ;
Shen, Chih-Chiu ;
Cheng, Chiao-Hung ;
Chen, Sih-Li .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2010, 33 (02) :251-258
[6]   Effects of fan-starting methods on the reverse-cycle defrost performance of an air-to-water heat pump [J].
Huang, D ;
Yuan, XL ;
Zhang, XQ .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2004, 27 (08) :869-875
[7]   Application of thermal battery in the ice storage air-conditioning system as a subcooler [J].
Huang, Ming-Chao ;
Chen, Bo-Ren ;
Hsiao, Ming-Jer ;
Chen, Sih-Li .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2007, 30 (02) :245-253
[8]   Design and rating of an integrated mechanical-subcooling vapor-compression refrigeration system [J].
Khan, JUR ;
Zubair, SM .
ENERGY CONVERSION AND MANAGEMENT, 2000, 41 (11) :1201-1222
[9]   Refrigeration system performance using liquid-suction heat exchangers [J].
Klein, SA ;
Reindl, DT ;
Brownell, K .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2000, 23 (08) :588-596
[10]   FROSTING PERFORMANCE OF TUBE FIN HEAT-EXCHANGERS WITH WAVY AND CORRUGATED FINS [J].
KONDEPUDI, SN ;
ONEAL, DL .
EXPERIMENTAL THERMAL AND FLUID SCIENCE, 1991, 4 (05) :613-618