Thermal characterization of intumescent fire retardant paints

被引:15
作者
Calabrese, L. [1 ]
Bozzoli, F. [1 ]
Bochicchio, G. [2 ]
Tessadri, B. [2 ]
Rainieri, S. [1 ]
Pagliarini, G. [1 ]
机构
[1] Univ Parma, Dept Ind Engn, Parco Area Sci 181-A, I-43124 Parma, Italy
[2] CNR, Trees & Timber Inst, I-38010 San Michele All Adige, Italy
来源
32ND UIT (ITALIAN UNION OF THERMO-FLUID-DYNAMICS) HEAT TRANSFER CONFERENCE | 2014年 / 547卷
关键词
CONE CALORIMETER;
D O I
10.1088/1742-6596/547/1/012005
中图分类号
O3 [力学];
学科分类号
08 ; 0801 ;
摘要
Intumescent coatings are now the dominant passive fire protection materials used in industrial and commercial buildings. The coatings, which usually are composed of inorganic components contained in a polymer matrix, are inert at low temperatures and at higher temperatures, they expand and degrade to provide a charred layer of low conductivity materials. The charred layer, which acts as thermal barrier, will prevent heat transfer to underlying substrate. The thermal properties of intumescent paints are often unknown and difficult to be estimated since they vary significantly during the expansion process; for this reason the fire resistance validation of a commercial coatings is based on expensive, large-scale methods where each commercial coating-beam configuration has to be tested one by one. Adopting, instead, approaches based on a thermal modelling of the intumescent paint coating could provide an helpful tool to make easier the test procedure and to support the design of fire resistant structures as well. The present investigation is focused on the assessment of a methodology intended to the restoration of the equivalent thermal conductivity of the intumescent layer produced under the action of a cone calorimetric apparatus. The estimation procedure is based on the inverse heat conduction problem approach, where the temperature values measured at some locations inside the layer during the expansion process are used as input known data. The results point out that the equivalent thermal conductivity reached by the intumescent material at the end of the expansion process significantly depends on the temperature while the initial thickness of the paint does not seem to have much effect.
引用
收藏
页数:10
相关论文
共 14 条
[1]   THERMAL-CONDUCTIVITY OF INTUMESCENT CHARS [J].
ANDERSON, CE ;
KETCHUM, DE ;
MOUNTAIN, WP .
JOURNAL OF FIRE SCIENCES, 1988, 6 (06) :390-410
[2]  
[Anonymous], 2001, 13631 UNI EN
[3]  
[Anonymous], 2013, 133814 UNI EN
[4]   Influence of external heat flux and coating thickness on the thermal insulation properties of two different intumescent coatings using cone calorimeter and numerical analysis [J].
Bartholmai, M ;
Schriever, R ;
Schartel, B .
FIRE AND MATERIALS, 2003, 27 (04) :151-162
[5]   Assessing the performance of intumescent coatings using bench-scaled cone calorimeter and finite difference simulations [J].
Bartholmai, M. ;
Schartel, B. .
FIRE AND MATERIALS, 2007, 31 (03) :187-205
[6]  
Beck J.V., 1985, Inverse Heat Conduction: Ill-Posed Problems
[7]   The Modeling of Heat Transfer across Intumescent Polymer Coatings [J].
Griffin, G. J. .
JOURNAL OF FIRE SCIENCES, 2010, 28 (03) :249-277
[8]   Assess the Fire Resistance of Intumescent Coatings by Equivalent Constant Thermal Resistance [J].
Li, Guo-Qiang ;
Lou, Guo-Biao ;
Zhang, Chao ;
Wang, Ling-Ling ;
Wang, Yong-Chang .
FIRE TECHNOLOGY, 2012, 48 (02) :529-546
[9]  
Mesquita L, 2007, FIRE RETARDANT COATI, VII
[10]  
Mesquita L, 2009, INTEGRITY RELIABILIT, P537