Quantitative comparison of partial discharge localization algorithms using time difference of arrival measurement in substation

被引:8
|
作者
Zhu, Ming-Xiao [1 ]
Wang, Yan-Bo [1 ]
Chang, Ding-Ge [1 ]
Zhang, Guan-Jun [1 ]
Tong, Xin [2 ]
Ruan, Ling [2 ]
机构
[1] Xi An Jiao Tong Univ, Sch Elect Engn, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Shaanxi, Peoples R China
[2] State Grid Hubei Elect Power Res Inst, Wuhan, Hubei, Peoples R China
基金
中国国家自然科学基金;
关键词
Air-insulated substation; Partial discharge; Antenna array; Localization algorithm; Quantitative comparison; PASSIVE SOURCE LOCALIZATION; AIR-INSULATED SUBSTATIONS; SWARM OPTIMIZATION; OF-ARRIVAL; LOCATION; RANGE; SYSTEMS; TDOA;
D O I
10.1016/j.ijepes.2018.06.036
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Partial discharge (PD) non-contact detection by using antenna array has gained extensive attention in air-insulated substation (AIS) monitoring. One significant superiority is that the positions of PD sources can be located by utilizing the differences of received signals. Also locating electromagnetic/acoustic radiative sources using passive sensor arrays is a continuous theme in the field of radar and sonar, and various localization methods have been developed. In this paper, we mainly concern the time difference localization techniques, which can be classified as maximum-likelihood (ML) and least squares (IS) estimators. The ML estimates positions by maximizing the probability density function, which is a high-nonlinear problem and difficult to be solved. The iteration or simplification solutions are proposed to give approximate ML results. As an alternative, LS estimators which can give closed-form solutions and with high computation efficiency are widely adopted. In this research, the theories and calculation procedures of several kinds of localization algorithms are reviewed, i.e., approximate ML, probability-based method, spherical-interpolation, Chan and squared range-difference LS, and their performances are compared by Monte Carlo simulation and experiments. The results indicate that probability based method presents highest accuracy and computation efficiency. Among other methods, Chan, bias-reduction and squared range-difference provide satisfying localization performance.
引用
收藏
页码:10 / 20
页数:11
相关论文
共 50 条
  • [1] Partial discharge position tracking method using a gis partial discharge signal and arrival time difference
    Choi, M.-G. (cmg8624@kepco.co.kr), 1600, Korean Institute of Electrical Engineers (62):
  • [2] A New Method for the Estimation of Time Difference of Arrival for Localization of Partial Discharge Sources using Acoustic Detection Technique
    Ghosh, R.
    Chatterjee, B.
    Dalai, S.
    2016 IEEE 7TH POWER INDIA INTERNATIONAL CONFERENCE (PIICON), 2016,
  • [3] Contributed Review: Source-localization algorithms and applications using time of arrival and time difference of arrival measurements
    Li, Xinya
    Deng, Zhiqun Daniel
    Rauchenstein, Lynn T.
    Carlson, Thomas J.
    REVIEW OF SCIENTIFIC INSTRUMENTS, 2016, 87 (04):
  • [4] Localization algorithms for asynchronous time difference of arrival positioning systems
    Shuai He
    Xiaodai Dong
    Wu-Sheng Lu
    EURASIP Journal on Wireless Communications and Networking, 2017
  • [5] Localization algorithms for asynchronous time difference of arrival positioning systems
    He, Shuai
    Dong, Xiaodai
    Lu, Wu-Sheng
    EURASIP JOURNAL ON WIRELESS COMMUNICATIONS AND NETWORKING, 2017,
  • [6] Quantitative Comparison of Partial Discharge Localization Algorithms on Power Transformers Based on Acoustic Method
    Wang, Yan-Bo
    Qin, Shao-Rui
    Wang, Liu-Fang
    Ding, Guo-Cheng
    Li, Jian-Lin
    Zhu, Tai-Yun
    Zhang, Guan-Jun
    2018 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (IEEE CEIDP), 2018, : 542 - 545
  • [7] Application of Time Difference of Arrival Methods in the Localization of Partial Discharge Sources Detected Using Bio-Inspired UHF Sensors
    Xavier, George V. R.
    de Oliveira, Adriano C.
    Silva, Allan D. C.
    Nobrega, Luiz A. M. M.
    da Costa, Edson G.
    Serres, Alexandre J. R.
    IEEE SENSORS JOURNAL, 2021, 21 (02) : 1947 - 1956
  • [8] Algorithms for arrival time estimation of partial discharge pulses in cable systems
    Wagenaars, P.
    Wouters, P. A. A. F.
    van der Wielen, P. C. J. M.
    Steennis, E. F.
    CONFERENCE RECORD OF THE 2008 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, 2008, : 694 - +
  • [9] Indoor Localization Using Ultrasonic Time Difference of Arrival
    Pang, Shuo
    Trujillo, Ricardo
    2013 PROCEEDINGS OF IEEE SOUTHEASTCON, 2013,
  • [10] Partial discharge and the measurement in gas insulated substation
    Han, Xiaolian
    Feng, Yunping
    Qiu, Yuchang
    Chen, Jinqing
    Hsi-An Chiao Tung Ta Hsueh/Journal of Xi'an Jiaotong University, 1995, 29 (03): : 30 - 38