Influence of Fault Parameters on Breaking Performance of Vacuum Circuit Breaker

被引:0
作者
Shu, Shengwen [1 ]
Ruan, Jiangjun [1 ]
Huang, Daochun [1 ]
机构
[1] Wuhan Univ, Sch Elect Engn, Wuhan 430072, Hubei Province, Peoples R China
来源
2013 2ND INTERNATIONAL CONFERENCE ON ELECTRIC POWER EQUIPMENT - SWITCHING TECHNOLOGY (ICEPE-ST) | 2013年
关键词
HIGH-CURRENT INTERRUPTION; AXIAL MAGNETIC-FIELD; NUMERICAL-SIMULATION; ARCS;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In order to analyze the influence of power system fault parameters on the breaking performance of vacuum circuit breaker (VCB), a black box model of VCB based on the diffuse vacuum arc interruption has been established in this paper. Taking the current zero as the demarcation point, arc voltage is modeled during the arcing period and post arc current (PAC) is modeled based on the theory of Langmuir probes during the post arc period. Based on this model, the equivalent discount factor of the breaking capability of VCB caused by the direct current (DC) component of short circuit current is evaluated using different methods. In addition, the post arc conductivity is used to represent the dielectric strength recovery of VCB, and the results show that the rate of rise of transient recovery voltage (TRV) mainly influences the post arc dielectric recovery rate after 1.5 mu s, while the rate of decrease of short circuit current prior to current zero only influences the initial post arc dielectric recovery rate. This model is expected to provide an effective way to predict the breaking performance of VCB.
引用
收藏
页数:4
相关论文
共 11 条
[1]   INVESTIGATION OF HIGH-CURRENT INTERRUPTION OF VACUUM CIRCUIT-BREAKERS [J].
DULLNI, E ;
SCHADE, E .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1993, 28 (04) :607-620
[2]   DIELECTRIC RECOVERY OF VACUUM ARCS AFTER STRONG ANODE SPOT ACTIVITY [J].
DULLNI, E ;
SCHADE, E ;
GELLERT, B .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 1987, 15 (05) :538-544
[3]   Numerical simulation of the residual charge of vacuum interrupters [J].
Gilles, R ;
Weltmann, KD ;
Schade, E ;
Claessens, M .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 2001, 29 (05) :754-758
[4]   On the effect of an axial magnetic field on the high-current vacuum arc [J].
Keidar, M ;
Schulman, MB .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 2000, 28 (01) :347-350
[5]   Vacuum interrupter model based on breaking tests [J].
Leusenkamp, MBJ .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 1999, 27 (04) :969-976
[6]   Physics of high-current interruption of vacuum circuit breakers [J].
Schade, E .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 2005, 33 (05) :1564-1575
[7]   Numerical simulation of high-current vacuum arcs with an external axial magnetic field [J].
Schade, E ;
Shmelev, DL .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 2003, 31 (05) :890-901
[8]   A PIC-MCC simulation of the high-voltage interruption ability of a vacuum interrupter [J].
Takahashi, Shinji ;
Arai, Kazuyoshi ;
Morimiya, Osami ;
Kaneko, Shuhei ;
Okabe, Shigemitsu .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 2007, 35 (04) :912-919
[9]   Vacuum circuit breaker postarc current modelling based on the theory of Langmuir probes [J].
van Lanen, Ezra P. A. ;
Smeets, Rene Peter Paul ;
Popov, Marjan ;
van der Sluis, Lou .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 2007, 35 (04) :925-932
[10]   Vacuum Circuit Breakers in Flexible AC Transmission Systems [J].
Wenzel, Timo ;
Leibfried, Thomas .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (01) :236-244