Elimination of Aperiodic Components of Measuring Elements of Relay Protection

被引:0
作者
Buryanina, Nadezhda [1 ]
Korolyuk, Yurii [1 ]
Koryakina, Maya [1 ]
Lesnykh, Elena [2 ]
Suslov, Konstantin [3 ]
机构
[1] North Eastern Fed Univ, Chukotka Branch, Anadyr, Russia
[2] Siberian Transport Univ, Novosibirsk, Russia
[3] Irkutsk Natl Res Tech Univ, Irkutsk, Russia
来源
2019 MODERN ELECTRIC POWER SYSTEMS (MEPS) | 2019年
基金
俄罗斯基础研究基金会;
关键词
Sinusoidal and aperiodic components; short-circuit current; positive; sequence current; negative-sequence current; relay protection; emergency conditions; fault location;
D O I
10.1109/MEPS46793.2019.9394978
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
In this paper, we propose algorithms to calculate the actual values of currents and their derivatives. The algorithms allow a sharp reduction in the aperiodic components of currents in the calculated actual values and their derivatives. Algorithms are developed to calculate the instantaneous values of positive- and negative-sequence currents when the information obtained during a time interval equal to two sinusoidal components of the currents in the presence of aperiodic components in the samples. To eliminate the disoperation of digital relay protection and improve the accuracy of fault location, it is necessary to eliminate the influence of aperiodic components in the currents drawn to the measuring devices of relay protection. The algorithm completely eliminates the aperiodic component at any time constants and is implemented by four samples of currents. The four samples of currents separated by three sampling intervals are sufficient for calculating all the parameters of currents, including the positive and negative-sequence currents, in particular in the case when the magnetic cores of current transformers reach saturation. The proposed methods for setting the industrial frequency parameters to avoid the aperiodic components in short-circuit currents are based on the algorithms that process the data from three and four samples of currents.
引用
收藏
页数:5
相关论文
共 15 条
  • [1] Bayliss C. R, 2012, RELAY PROTECTION TRA, VFourth, P287
  • [2] A review on issues and approaches for microgrid protection
    Brearley, Belwin J.
    Prabu, R. Raja
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2017, 67 : 988 - 997
  • [3] Buryanina N.S, 2019, P 2019 INT SCI TECHN P 2019 INT SCI TECHN
  • [4] Drozdov A.D, 1965, ENERGIYA
  • [5] Enhanced time overcurrent coordination
    Enríquez, AC
    Martínez, EV
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2006, 76 (6-7) : 457 - 465
  • [6] Evans E.J, 1970, IEEE TRANSL INSTRUME, Vim-19, P144
  • [7] Gergi B, 2019, DESIGN IMPLEMENTATIO, V135, P112
  • [8] Gurevich Vladimir, 2006, ELECT RELAYS PRINCIP
  • [9] Haeg H, 1965, BROWN BOVERI MITTEIL, V53, P326
  • [10] An overview of microgrid protection methods and the factors involved
    Hosseini, Seyed Amir
    Abyaneh, Hossein Askarian
    Sadeghi, Seyed Hossein Hesamedin
    Razavi, Farzad
    Nasiri, Adel
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2016, 64 : 174 - 186