Three-Stage Robust Inverter-Based Voltage/Var Control for Distribution Networks With High-Level PV

被引:154
作者
Zhang, Cuo [1 ,2 ]
Xu, Yan [2 ]
Dong, Zhaoyang [1 ,3 ]
Ravishankar, Jayashri [1 ]
机构
[1] Univ New South Wales, Sch Elect Engn & Telecommun, Sydney, NSW 2052, Australia
[2] Nanyang Technol Univ, Sch Elect & Elect Engn, Singapore 639798, Singapore
[3] China Southern Power Grid Res Inst, Guangzhou 510000, Guangdong, Peoples R China
关键词
Distribution networks; photovoltaic generation; robust optimization; voltage/var control; uncertainties; DISTRIBUTION CIRCUITS; VOLT/VAR CONTROL; OPTIMIZATION; CAPACITORS; POWER;
D O I
10.1109/TSG.2017.2752234
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a novel three-stage robust inverter-based voltage/var control (TRI-VVC) approach for high photovoltaic (PV)-penetrated distribution networks. The approach aims at coordinating three different control stages from centralized to local VVC to reduce energy loss and mitigate voltage deviation. In the first stage, capacitor banks and an on-load tap changer are scheduled hourly in a rolling horizon. In the second stage, PV inverters are dispatched in a short time-window. In the third stage, the inverters respond to real-time voltage violation through local droop controllers. A new PV inverter model for voltage control is developed to support both the centralized var dispatch and the local var droop control. To address uncertain PV output and load demand, a robust optimization (RO) model is proposed to optimize the first two stages while taking into account the droop voltage control support from the third stage. A linearized distribution power flow model with power loss is developed and applied in the RO. The simulation results show high efficiency and robustness of the proposed TRI-VVC strategy.
引用
收藏
页码:782 / 793
页数:12
相关论文
共 27 条
[1]   Exploring the Modeling Capacity of Two-Stage Robust Optimization: Variants of Robust Unit Commitment Model [J].
An, Yu ;
Zeng, Bo .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2015, 30 (01) :109-122
[2]  
[Anonymous], IEEE PES GEN M
[3]   HPC-Based Intelligent Volt/VAr Control of Unbalanced Distribution Smart Grid in the Presence of Noise [J].
Anwar, Adnan ;
Mahmood, A. N. ;
Taheri, Javid ;
Tari, Zahir ;
Zomaya, Albert Y. .
IEEE TRANSACTIONS ON SMART GRID, 2017, 8 (03) :1446-1459
[4]  
Ausgrid, 2014, DISTR GEN DISTR STOR
[5]   OPTIMAL SIZING OF CAPACITORS PLACED ON A RADIAL-DISTRIBUTION SYSTEM [J].
BARAN, ME ;
WU, FF .
IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (01) :735-743
[6]   Adaptive Robust Optimization for the Security Constrained Unit Commitment Problem [J].
Bertsimas, Dimitris ;
Litvinov, Eugene ;
Sun, Xu Andy ;
Zhao, Jinye ;
Zheng, Tongxin .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2013, 28 (01) :52-63
[7]  
Cuo Zhang, 2016, 2016 Power Systems Computation Conference (PSCC), P1, DOI 10.1109/PSCC.2016.7540822
[8]  
Gilbert GM, 1998, UNIVERSITY AND INDUSTRY - PARTNERS IN SUCCESS, CONFERENCE PROCEEDINGS VOLS 1-2, P850, DOI 10.1109/CCECE.1998.685631
[9]   Distributed Volt/VAr Control by PV Inverters [J].
Jahangiri, Pedram ;
Aliprantis, Dionysios C. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2013, 28 (03) :3429-3439
[10]   Autonomous and Adaptive Voltage Control Using Multiple Distributed Energy Resources [J].
Li, Huijuan ;
Li, Fangxing ;
Xu, Yan ;
Rizy, D. Tom ;
Adhikari, Sarina .