Modifications to ASHRAE's sizing method for vertical ground heat exchangers

被引:15
作者
Ahmadfard, Mohammadamin [1 ]
Bernier, Michel [1 ]
机构
[1] Polytech Montreal, Dept Mech Engn, CP 6079,Succ Ctr Ville, Montreal, PQ H3T 1J4, Canada
基金
加拿大自然科学与工程研究理事会;
关键词
SHORT-TIME ANALYSIS; DESIGN; VALIDATION;
D O I
10.1080/23744731.2018.1423816
中图分类号
O414.1 [热力学];
学科分类号
摘要
The current article proposes modifications to the ASHRAE sizing equation for vertical ground heat exchangers. The proposed method uses the same three pulse approach as the current sizing equation but uses g-functions to calculate the effective ground thermal resistances. One key feature of the iterative methodology is the ability to calculate new g-functions as the geometry morphs during the solution process. Long-term g-functions are evaluated analytically using the finite line source (FLS) solution over borehole segments while so-called short-term g-functions are calculated based on a hybrid analytical/numerical method to account for the borehole thermal capacity. The current article examines three aspects of the proposed methodology. First, it is shown that the time-consuming evaluation of the full g-function curve, typically obtained by temporal superposition, is not necessarily required. Second, the optimum number of borehole segments to obtain an accurate bore field length with reasonable calculation time is examined. The selection of a convergence criteria and its impact on calculation time is also discussed. The excellent agreement between results obtained with the proposed alternative method and the ones obtained from other design software tools confirms the validity of the proposed method. Finally, it is shown that short-term effects can have a relatively significant effect on the calculation of the required borehole length.
引用
收藏
页码:803 / 817
页数:15
相关论文
共 50 条
  • [21] Computational methods for ground thermal response of multiple borehole heat exchangers: A review
    Zhang, Changxing
    Wang, Yusheng
    Liu, Yufeng
    Kong, Xiangqiang
    Wang, Qing
    RENEWABLE ENERGY, 2018, 127 : 461 - 473
  • [22] A New Simulation Model for Vertical Spiral Ground Heat Exchangers Combining Cylindrical Source Model and Capacity Resistance Model
    Katsura, Takao
    Higashitani, Takashi
    Fang, Yuzhi
    Sakata, Yoshitaka
    Nagano, Katsunori
    Akai, Hitoshi
    Oe, Motoaki
    ENERGIES, 2020, 13 (06)
  • [23] Study of Ground Heat Exchangers in the Form of Parallel Horizontal Pipes Embedded in the Ground
    Neupauer, Krzysztof
    Pater, Sebastian
    Kupiec, Krzysztof
    ENERGIES, 2018, 11 (03):
  • [24] Decomposition and coupling of soil domain for modeling vertical ground heat exchangers using the state model size reduction technique
    Kim, Eui-Jong
    Roux, Jean-Jacques
    Kuznik, Frederic
    APPLIED THERMAL ENGINEERING, 2014, 69 (1-2) : 155 - 164
  • [25] Comparative analysis of U-pipe location on the sizing of borehole heat exchangers
    Zhang, Linfeng
    Luo, Xiaowei
    Huang, Gongsheng
    Zhang, Quan
    APPLIED THERMAL ENGINEERING, 2019, 150 : 666 - 673
  • [26] Research progress on the enhancement of heat transfer performance of ground heat exchangers: A review
    Wang, Ye
    Zhang, Luyu
    Zhang, Qiqiang
    Liu, Hengjian
    Lu, Zhi
    Heng, Zixin
    SUSTAINABLE ENERGY TECHNOLOGIES AND ASSESSMENTS, 2025, 76
  • [27] Experimental and numerical investigation of ground heat exchangers in the building foundation
    Kayaci, Nurullah
    Demir, Hakan
    Kanbur, Baris Burak
    Atayilmaz, Sevket Ozgur
    Agra, Ozden
    Acet, Rusen Can
    Gemici, Zafer
    ENERGY CONVERSION AND MANAGEMENT, 2019, 188 : 162 - 176
  • [28] PRINCIPLES OF MODELLING OF SLINKY-COIL GROUND HEAT EXCHANGERS
    Larwa, Barbara
    Kupiec, Krzysztof
    CHEMICAL AND PROCESS ENGINEERING-INZYNIERIA CHEMICZNA I PROCESOWA, 2020, 41 (02): : 81 - 93
  • [29] An adaptive segmentation Haar wavelet method for solving thermal resistance and capacity models of ground heat exchangers
    Nguyen, A.
    Pasquier, P.
    APPLIED THERMAL ENGINEERING, 2015, 89 : 70 - 79
  • [30] A transient quasi-3D entire time scale line source model for the fluid and ground temperature prediction of vertical ground heat exchangers (GHEs)
    Zhang, Linfeng
    Zhang, Quan
    Huang, Gongsheng
    APPLIED ENERGY, 2016, 170 : 65 - 75