General thermodynamic performance of irreversible absorption heat pump

被引:16
作者
Zhao Xiling [1 ]
Fu Lin [1 ]
Zhang Shigang [1 ]
机构
[1] Tsinghua Univ, Dept Bldg Sci, Beijing 100084, Peoples R China
关键词
Absorption heat pump; Irreversible; General performance; Thermodynamics; REFRIGERATORS; SYSTEMS;
D O I
10.1016/j.enconman.2010.07.023
中图分类号
O414.1 [热力学];
学科分类号
摘要
The absorption heat pump (AHP) was studied with thermodynamics. A four reservoirs model of absorption heat pump was established considering the heat resistance, heat leak and the internal irreversibility. The reasonable working regions, the performance effects of irreversibility, heat leak and the correlation of four components were studied. When studying the effects of internal irreversibility, two internal irreversibility parameters (I(he) for generator-absorber assembly and I(re) for evaporator-condenser assembly) were introduced to distinguish the different effects. When studying the heat transfer relations of four components, a universal relationship between the main parameters were deduced. The results which have more realized meaning show that, the reduction of the friction, heat loss, and internal dissipations of the evaporator-condenser assembly are more important than its reduction of generator-absorber assembly, and lessening the heat leak of generator are more important than its reduction of other components to improve the AHP performance. (C) 2010 Elsevier Ltd. All rights reserved.
引用
收藏
页码:494 / 499
页数:6
相关论文
共 11 条
[1]   Optimal performance analysis of irreversible cycles used as heat pumps and refrigerators [J].
Chen, JC .
JOURNAL OF PHYSICS D-APPLIED PHYSICS, 1997, 30 (04) :582-587
[2]   The general performance characteristics of an irreversible absorption heat pump operating between four temperature levels [J].
Chen, JC .
JOURNAL OF PHYSICS D-APPLIED PHYSICS, 1999, 32 (12) :1428-1433
[3]   EQUIVALENT COMBINED SYSTEMS OF 3-HEAT-SOURCE HEAT-PUMPS [J].
CHEN, JC ;
YAN, ZJ .
JOURNAL OF CHEMICAL PHYSICS, 1989, 90 (09) :4951-4955
[4]   Irreversible absorption heat-pump and its optimal performance [J].
Chen, LG ;
Qin, XY ;
Sun, FR ;
Wu, C .
APPLIED ENERGY, 2005, 81 (01) :55-71
[5]   Optimal coefficient of performance and heating load relationship of a three-heat-reservoir endoreversible heat pump [J].
Chen, LG ;
Wu, C ;
Sun, F .
ENERGY CONVERSION AND MANAGEMENT, 1997, 38 (08) :727-733
[6]   Laboratory research on combined cooling, heating and power (CCHP) systems [J].
Fu, L. ;
Zhao, X. L. ;
Zhang, S. G. ;
Jiang, Y. ;
Li, H. ;
Yang, W. W. .
ENERGY CONVERSION AND MANAGEMENT, 2009, 50 (04) :977-982
[7]   The effect of irreversibilities on the performance of a three-heat-source heat pump [J].
Goktun, S .
JOURNAL OF PHYSICS D-APPLIED PHYSICS, 1996, 29 (11) :2823-2825
[8]  
HEROLD KE, 1999, INT SORPT HEAT PUMP, P1
[9]   Local asymptotic stability of an irreversible heat pump subject to total thermal conductance constraint [J].
Huang, Yuewu .
ENERGY CONVERSION AND MANAGEMENT, 2009, 50 (06) :1444-1449
[10]   Thermoeconomic optimization for irreversible absorption refrigerators and heat pumps [J].
Kodal, A ;
Sahin, B ;
Ekmekci, I ;
Yilmaz, T .
ENERGY CONVERSION AND MANAGEMENT, 2003, 44 (01) :109-123