Performance of temperature and humidity independent control air-conditioning system in an office building

被引:150
作者
Zhao, Kang [1 ]
Liu, Xiao-Hua [1 ]
Zhang, Tao [1 ]
Jiang, Yi [1 ]
机构
[1] Tsinghua Univ, Dept Bldg Sci, Beijing 100084, Peoples R China
基金
中国国家自然科学基金;
关键词
THIC (temperature and humidity independent control); Dehumidification; Cooling; Performance; Air conditioning; DESICCANT; DEHUMIDIFICATION;
D O I
10.1016/j.enbuild.2011.03.041
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The temperature and humidity independent control (THIC) system, which controls indoor temperature and moisture separately, may be an attractive alternative to existing conventional HVAC systems for its prominent improvement on the overall system performance and utilization of low grade energy resources. In order to verify the effectiveness of THIC system, a pilot project has been implemented in an office building in Shenzhen, China. In the system, liquid desiccant fresh air handling units driven by heat pumps are utilized to remove the entire latent load of outdoor air supplied for the whole building, and chilled water at the temperature of 17.5 degrees C from chiller is pumped and distributed into dry fan coil units and radiant panels to control indoor temperature. This paper presents the results of field test of the system, which shows that the system can provide a comfortable indoor environment even in very hot and humid weather. The COP of the entire THIC system can reach 4.0. According to the energy usage data recorded from the year 2009, the energy consumption of the THIC system in the tested office building was 32.2 kWh/(m(2) yr), which demonstrates magnificent energy-saving potential compared with the conventional air-conditioning system (around 49 kWh/(m(2) yr)). (C) 2011 Elsevier B.V. All rights reserved.
引用
收藏
页码:1895 / 1903
页数:9
相关论文
共 15 条
  • [1] *ADSIQ, 2008, 179812007 AQSIQ SAC
  • [2] Ahmed CSK, 1997, APPL THERM ENG, V17, P125
  • [3] PERFORMANCE PREDICTIONS OF ALTERNATIVE, LOW-COST ABSORBENTS FOR OPEN-CYCLE ABSORPTION SOLAR COOLING
    AMEEL, TA
    GEE, KG
    WOOD, BD
    [J]. SOLAR ENERGY, 1995, 54 (02) : 65 - 73
  • [4] Chen XY, 2005, ASHRAE TRAN, V111, P277
  • [5] *DRYKOR LTD, 2001, AIR COND OUR DRY AIR
  • [6] Independent air dehumidification with membrane-based total heat recovery: Modeling and experimental validation
    Liang, C. H.
    Zhang, L. Z.
    Pei, L. X.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2010, 33 (02): : 398 - 408
  • [7] Annual performance of liquid desiccant based independent humidity control HVAC system
    Liu, Xiaohua
    Li, Zhen
    Jiang, Yi
    Lin, Borong
    [J]. APPLIED THERMAL ENGINEERING, 2006, 26 (11-12) : 1198 - 1207
  • [8] Performance analysis on a hybrid air-conditioning system of a green building
    Ma, Q
    Wang, RZ
    Dai, YJ
    Zhai, XQ
    [J]. ENERGY AND BUILDINGS, 2006, 38 (05) : 447 - 453
  • [9] Energy savings potential of chilled-ceiling combined with desiccant cooling in hot and humid climates
    Niu, JL
    Zhang, LZ
    Zuo, HG
    [J]. ENERGY AND BUILDINGS, 2002, 34 (05) : 487 - 495
  • [10] PERFORMANCE STUDIES FOR AN EXPERIMENTAL SOLAR OPEN-CYCLE LIQUID DESICCANT AIR DEHUMIDIFICATION SYSTEM
    PATNAIK, S
    LENZ, TG
    LOF, GOG
    [J]. SOLAR ENERGY, 1990, 44 (03) : 123 - 135