A Comparative Study of Methods for Estimating Virtual Flux at the Point of Common Coupling in Grid-Connected Voltage Source Converters With LCL Filter

被引:14
作者
Roslan, Nurul Fazlin [1 ,2 ]
Suul, Jon Are [3 ]
Rocabert, Joan [1 ]
Rodriguez, Pedro [1 ,4 ]
机构
[1] Tech Univ Catalonia, Res Ctr Renewable Elect Energy Syst SEER Ctr, Barcelona 08222, Spain
[2] Univ Kuala Lumpur, British Malaysian Inst, Gombak 53100, Malaysia
[3] SINTEF Energy Res, N-7465 Trondheim, Norway
[4] Loyola Univ Andalusia, Seville 41014, Spain
关键词
LCL filter; proportional resonant (PR) current controller; virtual flux (VF) estimation; voltage source converter (VSC); DIRECT POWER-CONTROL; 3-PHASE PWM RECTIFIERS; IMPLEMENTATION; INTEGRATION;
D O I
10.1109/TIA.2017.2743200
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Grid synchronization based on virtual flux (VF) estimation allows for control of grid-connected power converter without depending on ac-voltage measurements. This is useful in voltage-sensor-less applications for reducing cost and complexity of the control hardware, and can be utilized in case of limited reliability or availability of voltage measurements at the intended point of synchronization to the grid. However, for voltage source converters (VSC) with LCL filters, the influence of the capacitor current must be taken into account to ensure accurate VF estimation at the point of common coupling (PCC) with the grid. This paper presents a comparative evaluation of three VF-based methods for grid synchronization of VSCs with LCL filters, with three different ways of obtaining the capacitor current. The VF estimation in the first method is based only on the measured converter currents. The second method includes capacitor voltage measurements used for estimating the capacitor currents, while the capacitor currents are measured in the third approach. Comparative results from time-domain simulations are presented, demonstrating good performance of the estimation and accurate control of the active and reactive power at the PCC with all three methods, as long as sufficiently accurate filter parameters and current measurements are available. However, the approach based on capacitor current measurements is sensitive to noise due to the high ripple current compared with the fundamental frequency current in the capacitors. The operation of a converter with VF-based grid synchronization including estimation of the capacitor current is demonstrated by experimental results, verifying the voltage sensor-less operation with LCL filter.
引用
收藏
页码:5795 / 5809
页数:15
相关论文
共 38 条
[1]  
[Anonymous], P IEEE INT C INN SMA
[2]   Virtual-Flux-Based Predictive Direct Power Control of AC/DC Converters With Online Inductance Estimation [J].
Antoniewicz, Patrycjusz ;
Kazmierkowski, Marian P. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2008, 55 (12) :4381-4390
[3]  
Boyra M., 2011, Proceedings of the 2011 14th European Conference on Power Electronics and Applications, P1
[4]  
Davari M., 2016, IEEE T POWER ELECTR, V8993, P1
[5]  
Eskandari-Torbati H, 2015, 2015 6TH POWER ELECTRONICS, DRIVES SYSTEMS & TECHNOLOGIES CONFERENCE (PEDSTC), P375, DOI 10.1109/PEDSTC.2015.7093304
[6]   Low computational burden grid voltage estimation for grid connected voltage source converter-based power applications [J].
Gholami-Khesht, Hosein ;
Monfared, Mohammad ;
Golestan, Saeed .
IET Power Electronics, 2015, 8 (05) :656-664
[7]   Improving the Dynamics of Virtual-Flux-Based Control of Three-Phase Active Rectifiers [J].
Gonzalez Norniella, Joaquin ;
Cano, Jose M. ;
Alonso Orcajo, Gonzalo ;
Rojas, Carlos H. ;
Francisco Pedrayes, Joaquin ;
Cabanas, Manes F. ;
Melero, Manuel G. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2014, 61 (01) :177-187
[8]  
Gullvik William, 2007, 2007 European Conference on Power Electronics and Applications, P1, DOI 10.1109/EPE.2007.4417734
[9]  
Gullvik W., 2007, THESIS
[10]   A Synchronization Method for Single-Phase Grid-Tied Inverters [J].
Hadjidemetriou, Lenos ;
Kyriakides, Elias ;
Yang, Yongheng ;
Blaabjerg, Frede .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2016, 31 (03) :2139-2149