Practical Calculation Method for the Short-Circuit Current of Power Grids with High Temperature Superconducting Fault Current Limiters

被引:3
|
作者
Hong, Hai-feng [1 ]
Yu, Meng-ze [1 ]
Zhang, Xiao-hui [1 ]
Huan, Jia-jia [1 ]
Sui, Yu [1 ]
Pan, Xian-xian [1 ]
机构
[1] Guangdong Power Grid Co Ltd, Grid Planning & Res Ctr, Guangzhou, Guangdong, Peoples R China
基金
国家高技术研究发展计划(863计划);
关键词
Electromechanical transient; High-temperature superconducting fault current limiter; Nonlinear impedance-current characteristic; Short-circuit current calculation; STABILITY; TRANSMISSION;
D O I
10.1007/s42835-019-00295-7
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
With the expansion of the power grid scale and the enhancement of network structure interconnection, the short-circuit current of power grids is increasingly close to the upper capacity limit of circuit breakers. The fault current limiter is effective in suppressing the short-circuit current of power grids, and with the mature development of superconducting technology, high-temperature superconducting fault current limiters (HTS-FCLs) have been widely used in power grids. Due to the nonlinear impedance-current characteristic of HTS-FCLs, the traditional short-circuit current calculation method is inapplicable to power grids with HTS-FCLs. First, based on the establishment of the electromechanical transient model and the short-circuit calculation model, the short-circuit current calculation procedure for power grids with HTS-FCLs is proposed. Second, the calculation methods for three-phase and single-phase short-circuit currents at the substation bus in power grids with HTS-FCLs are analyzed. Finally, three-phase and single-phase short-circuit currents at the 500 kV Xijiang substation bus in the Guangdong power grid are calculated as the study case. Simulation results show that compared with the situation where there is no HTS-FCL installed, the short-circuit current on the 500 kV bus decreases from 65.34 to 58.31 kA in terms of the three-phase short-circuit fault, and decreases from 54.56 to 46.62 kA in terms of the single-phase short-circuit fault, thus verifying the effectiveness and practicability of HTS-FCLs in suppressing the short-circuit current, which is significant for the safe, stable and reliable operation of the power grid.
引用
收藏
页码:945 / 953
页数:9
相关论文
共 50 条
  • [41] Impact on Superconducting Fault Current Limiters on Circuit Breaker Capability
    Bahirat, H. J.
    Khaparde, S. A.
    Kodle, S.
    Dabeer, V.
    2016 NATIONAL POWER SYSTEMS CONFERENCE (NPSC), 2016,
  • [42] Short-circuit current limitation by superconducting transformer
    Janowski, Tadeusz
    Wojtasiewicz, Grzegorz
    Jaroszynski, Leszek
    2016 13TH SELECTED ISSUES OF ELECTRICAL ENGINEERING AND ELECTRONICS (WZEE), 2016,
  • [43] High temperature superconducting fault current limiters as enabling technology in electrical grids with increased distributed generation penetration
    Pina J.M.
    Neves M.V.
    Álvarez A.
    Rodrigues A.L.
    IFIP Advances in Information and Communication Technology, 2010, 314 : 427 - 434
  • [44] Short-circuit current calculation method for AC/DC power transmission systems with MMC
    Gao, Yiying
    Han, Yi
    Liu, Xinyu
    Xu, Zheng
    Zhang, Shang
    Zhang, Yuhong
    Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2022, 43 (08): : 17 - 23
  • [45] High Temperature Superconducting Fault Current Limiters as Enabling Technology in Electrical Grids with Increased Distributed Generation Penetration
    Pina, Joao Murta
    Neves, Mario Ventim
    Alvarez, Alfredo
    Rodrigues, Amadeu Leao
    EMERGING TRENDS IN TECHNOLOGICAL INNOVATION, 2010, 314 : 427 - +
  • [46] SUPERCONDUCTING FAULT CURRENT LIMITERS - A NEW DEVICE FOR FUTURE SMART GRIDS
    Bock, Joachim
    Hobl, Achim
    Schramm, Judith
    2012 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2012,
  • [47] Fault Current Limitation Coordination in Electric Power Grid With Superconducting Fault Current Limiters
    Hayakawa, Naoki
    Maeno, Yuya
    Kojima, Hiroki
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2018, 28 (04)
  • [48] Study of reducing losses, short-circuit currents and harmonics by allocation of distributed generation, capacitor banks and fault current limiters in distribution grids
    Azeredo, Lucas F. S.
    Yahyaoui, Imene
    Fiorotti, Rodrigo
    Fardin, Jussara F.
    Garcia-Pereira, Hilel
    Rocha, Helder R. O.
    APPLIED ENERGY, 2023, 350
  • [49] Modeling of Current-Limiting Circuit Breakers for the Calculation of Short-Circuit Current
    Wu, Huaren
    Yuan, Ling
    Sun, Lin
    Li, Xiaohui
    IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (02) : 652 - 656
  • [50] Short-circuit Current Characteristics of Distributed Power and Fault Location Method after Distributed Power is Connected
    Zhao Dan
    Zhang Xinyu
    Wang Yang
    Tian Ye
    Wang Yanan
    Lang Yexing
    2020 5TH ASIA CONFERENCE ON POWER AND ELECTRICAL ENGINEERING (ACPEE 2020), 2020, : 1782 - 1786