Practical Calculation Method for the Short-Circuit Current of Power Grids with High Temperature Superconducting Fault Current Limiters

被引:3
|
作者
Hong, Hai-feng [1 ]
Yu, Meng-ze [1 ]
Zhang, Xiao-hui [1 ]
Huan, Jia-jia [1 ]
Sui, Yu [1 ]
Pan, Xian-xian [1 ]
机构
[1] Guangdong Power Grid Co Ltd, Grid Planning & Res Ctr, Guangzhou, Guangdong, Peoples R China
基金
国家高技术研究发展计划(863计划);
关键词
Electromechanical transient; High-temperature superconducting fault current limiter; Nonlinear impedance-current characteristic; Short-circuit current calculation; STABILITY; TRANSMISSION;
D O I
10.1007/s42835-019-00295-7
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
With the expansion of the power grid scale and the enhancement of network structure interconnection, the short-circuit current of power grids is increasingly close to the upper capacity limit of circuit breakers. The fault current limiter is effective in suppressing the short-circuit current of power grids, and with the mature development of superconducting technology, high-temperature superconducting fault current limiters (HTS-FCLs) have been widely used in power grids. Due to the nonlinear impedance-current characteristic of HTS-FCLs, the traditional short-circuit current calculation method is inapplicable to power grids with HTS-FCLs. First, based on the establishment of the electromechanical transient model and the short-circuit calculation model, the short-circuit current calculation procedure for power grids with HTS-FCLs is proposed. Second, the calculation methods for three-phase and single-phase short-circuit currents at the substation bus in power grids with HTS-FCLs are analyzed. Finally, three-phase and single-phase short-circuit currents at the 500 kV Xijiang substation bus in the Guangdong power grid are calculated as the study case. Simulation results show that compared with the situation where there is no HTS-FCL installed, the short-circuit current on the 500 kV bus decreases from 65.34 to 58.31 kA in terms of the three-phase short-circuit fault, and decreases from 54.56 to 46.62 kA in terms of the single-phase short-circuit fault, thus verifying the effectiveness and practicability of HTS-FCLs in suppressing the short-circuit current, which is significant for the safe, stable and reliable operation of the power grid.
引用
收藏
页码:945 / 953
页数:9
相关论文
共 50 条
  • [31] Influence of reactive power support control strategy on short-circuit current calculation and fault analysis method of DFIG
    Yin, Jun
    ENERGY REPORTS, 2021, 7 : 5933 - 5942
  • [32] Practical calculation of short-circuit current of DFIG considering crowbar resistance
    Yang G.
    Pan W.
    Liu M.
    Yang C.
    1600, Power System Technology Press (40): : 2075 - 2080
  • [33] A Wind Farm Short-Circuit Current Calculation Practical Model Applied to High Voltage Power Grid Simulation
    Wang, Xiaohai
    Pan, Xianxian
    Wan, Jiang
    Qi, Jun
    Zhang, Hongguang
    Li, Shitong
    PROCEEDINGS OF THE 2014 INTERNATIONAL CONFERENCE ON MECHATRONICS, ELECTRONIC, INDUSTRIAL AND CONTROL ENGINEERING, 2014, 5 : 1493 - +
  • [34] A Pole-to-Pole Short-Circuit Fault Current Calculation Method for DC Grids (vol 32, pg 4943, 2017)
    Li, Chengyu
    Zhao, Chengyong
    Xu, Jianzhong
    Ji, Yuke
    Zhang, Fan
    An, Ting
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2019, 34 (01) : 826 - 826
  • [35] Modeling and simulation of high temperature resistive superconducting fault current limiters
    Ye, L
    Juengst, KP
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2004, 14 (02) : 839 - 842
  • [36] Optimal placement of resistive superconducting fault current limiter by considering short-circuit current and transient stability of power system
    Hafidz, Isa
    Mahendra, Rafin Aqsa Izza
    Pujiantara, Margo
    Priyadi, Ardyono
    Purnomo, Mauridhi Hery
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2023, 17 (19) : 4304 - 4315
  • [37] ADPSS Based Short-circuit Current Calculation Method of MMC
    Yu, Xiao
    Wang, Shanshan
    Zhao, Bing
    Su, Zhida
    Wang, Hongfu
    Peng, Hongying
    2021 11TH INTERNATIONAL CONFERENCE ON POWER, ENERGY AND ELECTRICAL ENGINEERING (CPEEE 2021), 2021, : 20 - 25
  • [38] IMPROVED MPPT SHORT-CIRCUIT CURRENT METHOD BY A FUZZY SHORT-CIRCUIT CURRENT ESTIMATOR
    Diaz, Nelson
    Luna, Adriana
    Duarte, Oscar
    2011 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2011, : 211 - 218
  • [39] Practical Engineering Calculation of Short-circuit Current for Renewable Energy Based on Local Iteration of Fault Area
    Jia K.
    Hou L.
    Bi T.
    Li Y.
    Qin H.
    Ding X.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2021, 45 (13): : 151 - 158
  • [40] Practical Calculation for Bipolar Short-circuit Fault Current of Transmission Line in MMC-HVDC Grid
    Hao L.
    Li W.
    Wang Z.
    Gu Y.
    Wang G.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2020, 44 (05): : 68 - 76