Protection coordination scheme for directional overcurrent relays considering change in network topology and OLTC tap position

被引:33
作者
Alam, Mahamad Nabab [1 ]
Das, Biswarup [2 ]
Pant, Vinay [2 ]
机构
[1] Indian Inst Technol, Dept Elect Engn, Kanpur 208016, Uttar Pradesh, India
[2] Indian Inst Technol, Dept Elect Engn, Roorkee 247667, Uttar Pradesh, India
关键词
Contingency; Directional overcurrent relays; Interior point method; Protection coordination; DISTRIBUTED GENERATION; SEARCH ALGORITHM; OPTIMIZATION;
D O I
10.1016/j.epsr.2020.106395
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a robust protection coordination scheme of directional overcurrent relays (DOCRs) for multiple network topologies in the presence of on-load tap changers (OLTCs). The robust protection coordination scheme provides single settings of DOCRs which will be valid for all N - 1 contingencies created after outage of a line, transformer or generator. An efficient constraint reduction strategy is introduced to reduce the number of coordination constraints caused by consideration of multiple topologies. The impact of tap positions of the OLTCs has been incorporated in the required steady-state and short-circuit current calculations. The robust protection coordination scheme has been posed as an optimization problem and solved using an interior point method based algorithm. The feasibility and the effectiveness of the proposed formulation and solution algorithm has been demonstrated on the IEEE 14-bus power system network.