Measurement of the magnetic fields of high-voltage substations (230 kV) in Tehran (Iran) and comparison with the ACGIH treshold limit values

被引:12
作者
Fard, Mahdieh Sharifi [1 ]
Nasiri, Parvin [2 ]
Monazzam, Mohammad Reza [2 ]
机构
[1] Isalmic Azad Univ, Fac Environm & Energy, Sci & Res Branch, Tehran, Iran
[2] Univ Tehran Med Sci, Dept Occupat Hlth, Sch Hlth, Tehran, Iran
关键词
D O I
10.1093/rpd/ncq445
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Measurements were made according to IEEE standard 644-1994 at a height of 1 m above floor level. It is concluded that none of the measurements exceeded the ACGIH threshold limit value. Among all control rooms the highest measured density amount is 0.69 mu T in the control room of Ozgol substation and the lowest is 0.2 mu T in the post of Shahid Firouzi. The control room of Ozgol substation is located in the second floor and bus-bars are located at a short distance from the window on the east, and so the highest recorded magnetic field is measured in this control room. Among all switchgear parts the highest amount 9.15 mu T is measured in Kan substation. None of the measurements exceeded the ACGIH threshold limit value.