Evaluating Distributed PV Curtailment Using Quasi-Static Time-Series Simulations

被引:6
作者
Azzolini, Joseph A. [1 ]
Reno, Matthew J. [1 ]
Gurule, Nicholas S. [2 ]
Horowitz, Kelsey A. W. [3 ]
机构
[1] Sandia Natl Labs, Elect Power Syst Res Grp, Albuquerque, NM 87123 USA
[2] Sandia Natl Labs, Renewable & Distributed Syst Integrat Grp, Albuquerque, NM 87123 USA
[3] Natl Renewable Energy Lab, Power Syst Engn Ctr, Golden, CO 80401 USA
来源
IEEE OPEN ACCESS JOURNAL OF POWER AND ENERGY | 2021年 / 8卷
关键词
Advanced inverter; autonomous volt-var; curtailment; distribution system analysis; PV grid integration; quasi-static time-series; POWER CURTAILMENT; INVERTERS;
D O I
10.1109/OAJPE.2021.3111821
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
By strategically curtailing active power and providing reactive power support, photovoltaic (PV) systems with advanced inverters can mitigate voltage and thermal violations in distribution networks. Quasi-static time-series (QSTS) simulations are increasingly being utilized to study the implementation of these inverter functions as alternatives to traditional circuit upgrades. However, QSTS analyses can yield significantly different results based on the availability and resolution of input data and other modeling considerations. In this paper, we quantified the uncertainty of QSTS-based curtailment evaluations for two different grid-support functions (autonomous Volt-Var and centralized PV curtailment for preventing reverse power conditions) through extensive sensitivity analyses and hardware testing. We found that Volt-Var curtailment evaluations were most sensitive to poor inverter convergence (-56.4%), PV time-series data (-18.4% to +16.5%), QSTS resolution (-15.7%), and inverter modeling uncertainty (+14.7%), while the centralized control case was most sensitive to load modeling (-26.5% to +21.4%) and PV time-series data (-6.0% to +12.4%). These findings provide valuable insights for improving the reliability and accuracy of QSTS analyses for evaluating curtailment and other PV impact studies.
引用
收藏
页码:365 / 376
页数:12
相关论文
共 36 条
  • [1] [Anonymous], 2012, 10180 GOST, DOI 10.1109/SECon.2012.6196924
  • [2] [Anonymous], 2013, SAINT V8 34A
  • [3] [Anonymous], 2017, P INT C INT ADV SYST
  • [4] ASTM, 2018, STANDARD SPECIFICATI, DOI DOI 10.1520/C0033_C0033M-18
  • [5] Optimal Settings for Multiple Groups of Smart Inverters on Secondary Systems Using Autonomous Control
    Bello, Mobolaji
    Montenegro-Martinez, Davis
    York, Ben
    Smith, Jeff
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2018, 54 (02) : 1218 - 1223
  • [6] Coordinated Use of Smart Inverters With Legacy Voltage Regulating Devices in Distribution Systems With High Distributed PV Penetration-Increase CVR Energy Savings
    Ding, Fei
    Baggu, Murali M.
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2023, 14 (03) : 1804 - 1813
  • [7] Estimation of solar photovoltaic energy curtailment due to volt-watt control
    Emmanuel, Michael
    Giraldez, Julieta
    Gotseff, Peter
    Hoke, Anderson
    [J]. IET RENEWABLE POWER GENERATION, 2020, 14 (04) : 640 - 646
  • [8] EPRI, OP DISTR SYST SIM OP
  • [9] Distribution Voltage Regulation Through Active Power Curtailment With PV Inverters and Solar Generation Forecasts
    Ghosh, Shibani
    Rahman, Saifur
    Pipattanasomporn, Manisa
    [J]. IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2017, 8 (01) : 13 - 22
  • [10] Giraldez J, 2018, NRELTP5D0072298