Research on Optimal D-PMU Placement Technology to Improve the Observability of Smart Distribution Networks

被引:7
作者
Kong, Xiangyu [1 ]
Yuan, Xiaoxiao [1 ]
Wang, Yuting [1 ]
Xu, Yong [1 ]
Yu, Li [2 ,3 ]
机构
[1] Tianjin Univ, Minist Educ, Key Lab Smart Grid, Tianjin 300072, Peoples R China
[2] China Southern Power Grid, Elect Power Res Inst, Guangzhou 510080, Guangdong, Peoples R China
[3] China Southern Power Grid, Digital Grid Res Inst, Guangzhou 510080, Guangdong, Peoples R China
关键词
optimal distribution phasor measurement unit placement; observability; bus vulnerability; measurement redundancy; unobservable depth; assistant decision-making software; PHASOR MEASUREMENT UNITS; POWER; VOLTAGE; PROTECTION; ALGORITHM; ROBUST;
D O I
10.3390/en12224297
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
With the continuous development of smart distribution networks, their observable problems have become more serious. Research on the optimal placement of the distribution phasor measurement unit (D-PMU) is an important way to improve the measurability, observability and controllability of a smart distribution network. In this paper, the optimal D-PMU placement methods and implementation technology were studied to determine the optimal D-PMU placement scheme. Considering the bus vulnerability index and the different operating states of the system, the more practical one-time optimal placement methods to ensure complete system observability was proposed. On this basis, the system's measurement redundancy and unobservable depth were considered to realize the multistage optimal D-PMU placement. The corresponding mathematical model and solution flow were given. Then the implementation technology of the methods was studied and the optimal D-PMU placement assistant decision-making software for smart distribution network was developed. Thereby, the structure and requirements of different distribution networks can be satisfied. The application analysis, functional architecture and the overall design process were given. Finally, the methods and software were analyzed by using the IEEE 33 bus system and an actual project, the Guangzhou Nansha Yuan'an Substation. The verification results showed that the method and software mentioned in this paper can provide convenient and quick operation for optimal D-PMU placement, improve the efficiency of smart distribution network planning work, and promote the theoretical application level of smart distribution network planning results.
引用
收藏
页数:23
相关论文
共 39 条
  • [1] Optimal PMU Placement Based on Probabilistic Cost/Benefit Analysis
    Aminifar, Farrokh
    Fotuhi-Firuzabad, Mahmud
    Safdarian, Amir
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2013, 28 (01) : 566 - 567
  • [2] Probabilistic Multistage PMU Placement in Electric Power Systems
    Aminifar, Farrokh
    Fotuhi-Firuzabad, Mahmud
    Shahidehpour, Mohammad
    Khodaei, Amin
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (02) : 841 - 849
  • [3] [Anonymous], 2014, 2014 CLEMS U POW SYS
  • [4] Optimal Integration of Phasor Measurement Units in Power Systems Considering Conventional Measurements
    Azizi, S.
    Gharehpetian, G. B.
    Dobakhshari, A. Salehi
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2013, 4 (02) : 1113 - 1121
  • [5] A hybrid procedure to design a wide-area damping controller robust to permanent failure of the communication channels and power system operation uncertainties
    Bento, Murilo E. C.
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2019, 110 : 118 - 135
  • [6] Chen XB, 2016, 2016 IEEE INNOVATIVE SMART GRID TECHNOLOGIES - ASIA (ISGT-ASIA), P559, DOI 10.1109/ISGT-Asia.2016.7796445
  • [7] [丁明 Ding Ming], 2015, [电工技术学报, Transactions of China Electrotechnical Society], V30, P214
  • [8] Ding Shaoqian, 2017, Electrical Measurement and Instrumentation, V54, P28
  • [9] PMU-assisted overcurrent protection for distribution feeders employing Solid State Transformers
    Hooshyar, H.
    Baran, M. E.
    Firouzi, S. R.
    Vanfretti, L.
    [J]. SUSTAINABLE ENERGY GRIDS & NETWORKS, 2017, 10 : 26 - 34
  • [10] Jamuna K., 2011, Proceedings of the International Conference on Sustainable Energy and Intelligent Systems (SEISCON 2011), P384, DOI 10.1049/cp.2011.0394