Fault Location Scheme for Abnormal Grounding Point in Isolated Ground Wire of Large-Scale Clean Energy Transmission

被引:1
|
作者
Wang, Yunlong [1 ]
Chen, Nuo [1 ]
Ma, Xiangnan [1 ]
Yang, Zongzhang [1 ]
机构
[1] China Southern Power Grid EHV Transmiss Co, Kunming, Yunnan, Peoples R China
关键词
rising of current; de-icing; isolated ground wire; earthing switch; fault location; LINES;
D O I
10.3389/fenrg.2021.702245
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
There is a large number of grounding switches along the isolated ground wire for the de-icing in the large-scale wind farm. If any of these grounding switches are left open by accident, this can create an unexpected abnormal grounding point in the isolated ground wire. Based on the analysis of the output power of de-icing devices, the output power of different poles can be applied for the abnormal grounding point fault location. Since the rise of output current to the rated current of de-icing devices requires a long time to build up, the protective relay may lock the de-icing device before the output current reaches the rated current. Thus, the ratio of output energy of two poles can be selected to locate the abnormal grounding point. This study verified this location method by conducting a large number of simulations.
引用
收藏
页数:8
相关论文
共 2 条
  • [1] An improved reflectometry-based fault location scheme for suppressing multiple reflections in large-scale photovoltaic strings
    Su, Weihong
    Gao, Dedong
    Wang, Shan
    Wang, Yongxin
    Zhao, Desheng
    Zhang, Shuai
    SOLAR ENERGY, 2024, 270
  • [2] Identification of Permanent Faults and Disturbance Induced by Deicing Based on Permutation Entropy for the Large-Scale Clean Energy Transmission in Winter
    Wang, Yunlong
    Tang, Tiejun
    Ju, Xiang
    Hong, Dingding
    MATHEMATICAL PROBLEMS IN ENGINEERING, 2021, 2021