Ventilation efficiencies and thermal comfort results of a desk-edge-mounted task ventilation system

被引:38
作者
Faulkner, D [1 ]
Fisk, WJ [1 ]
Sullivan, DP [1 ]
Lee, SM [1 ]
机构
[1] Univ Calif Berkeley, Lawrence Berkeley Lab, Indoor Environm Dept, Environm Energy Technol Div, Berkeley, CA 94720 USA
关键词
improved IAQ practices and technologies; ventilation rates and strategies; offices; perceived air quality; thermal comfort;
D O I
10.1111/j.1600-0668.2004.00295.x
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In chamber experiments, we investigated the ventilation effectiveness and thermal comfort of a task ventilation system with an air supply nozzle located underneath the front edge of a desk and directing air towards a heated mannequin or a human volunteer seated at the desk. The task ventilation system provided outside air, while another ventilation system provided additional space cooling but no outside air. Test variables included the vertical angle of air supply (-15degrees to 45degrees from horizontal), and the supply flow rate of (3.5-6.5 l/s). Using the tracer gas step-up and step-down procedures, the measured air change effectiveness (i.e., exhaust air age divided by age of air in the breathing zone) in experiments with the mannequin ranged from 1.4 to 2.7 (median, 1.8), whereas with human subjects the air change effectiveness ranged from 1.3 to 2.3 (median, 1.6). The majority of the air change effectiveness values with the human subjects were less than values with the mannequin using comparable tests. Similarly, the tests run with supply air temperature equal to the room air temperature had lower air change effectiveness values than comparable tests with the supply air temperature lower (similar to5degreesC) than the room air temperature. The air change effectiveness values are higher than typically reported for commercially-available task ventilation or displacement ventilation systems. Based on surveys completed by the subjects, operation of the task ventilation system did not cause thermal discomfort.
引用
收藏
页码:92 / 97
页数:6
相关论文
共 50 条
  • [41] Assessment of Thermal Comfort in Rooms Equipped with a Decentralised Facade Ventilation Unit
    Zender-Swiercz, Ewa
    Telejko, Marek
    Galiszewska, Beata
    Starzomska, Mariola
    ENERGIES, 2022, 15 (19)
  • [42] Investigation of effects of window combinations on ventilation characteristics for thermal comfort in buildings
    Hassan, M. A.
    Guirguis, N. M.
    Shaalan, M. R.
    El-Shazly, K. M.
    DESALINATION, 2007, 209 (1-3) : 251 - 260
  • [43] Ventilation performance index fully considering effects of ventilation air parameters on thermal comfort: Effective Draft - Moisture Temperature
    Zhang, Sheng
    Zhang, Xia
    Lin, Zhang
    Fang, Zhaosong
    ENERGY AND BUILDINGS, 2024, 308
  • [44] Impact of indoor heat load and natural ventilation on thermal comfort of radiant cooling system: An experimental study
    Dharmasastha K.
    Samuel D.G.L.
    Nagendra S.M.S.
    Maiya M.P.
    Energy and Built Environment, 2023, 4 (05): : 543 - 556
  • [45] Simplified model for thermal comfort, IAQ and energy savings in rooms conditioned by displacement ventilation aided with transient personalized ventilation
    Al Assaad, Douaa
    Habchi, Carine
    Ghali, Kamel
    Ghaddar, Nesreen
    ENERGY CONVERSION AND MANAGEMENT, 2018, 162 : 203 - 217
  • [46] THERMAL COMFORT AND ENERGY SAVINGS IN A SIMULATED OFFICE CONDITIONED BY A TRANSIENT PERSONALIZED VENTILATOR AND A DISPLACEMENT VENTILATION SYSTEM
    Al Assad, Douaa
    Ghali, Kamel
    Ghaddar, Nesreen
    Katramiz, Elvire
    PROCEEDINGS OF THE ASME 2020 HEAT TRANSFER SUMMER CONFERENCE (HT2020), 2020,
  • [47] A comparison of the thermal comfort performances of a radiation floor cooling system when combined with a range of ventilation systems
    Liu, Jiying
    Li, Zhuangzhuang
    Kim, Moon Keun
    Zhu, Shengwei
    Zhang, Linhua
    Srebric, Jelena
    INDOOR AND BUILT ENVIRONMENT, 2020, 29 (04) : 527 - 542
  • [48] Experimental evaluation of an intermittent air supply system - Part 1: Thermal comfort and ventilation efficiency measurements
    Kabanshi, Alan
    Wigo, Hans
    Sandberg, Mats
    BUILDING AND ENVIRONMENT, 2016, 95 : 240 - 250
  • [49] Displacement ventilation system with celling mounted diffusers in a gas commercial kitchen
    Okuda A.
    Kondo Y.
    Yoshino H.
    Yamashita S.
    Kawazoe T.
    2018, Architectural Institute of Japan (83): : 839 - 849
  • [50] Study on Thermal Comfort and Indoor Air Quality in the Classroom with System Air-conditioner and Ventilation System for Cooling Loads
    Noh, Kwang-Chul
    Jang, Jae-Soo
    Oh, Myung-Do