Continuous IEQ monitoring system: Performance specifications and thermal comfort classification

被引:60
作者
Parkinson, Thomas [1 ,2 ]
Parkinson, Alex [3 ]
de Dear, Richard [1 ]
机构
[1] Univ Sydney, Indoor Environm Qual Lab, Sch Architecture Design & Planning, Sydney, NSW 2006, Australia
[2] Univ Calif Berkeley, CBE, Berkeley, CA 94720 USA
[3] Macquarie Univ, Dept Math, Sydney, NSW, Australia
基金
新加坡国家研究基金会;
关键词
Indoor environmental quality; Continuous monitoring; Building performance; Sensors; Standards; Thermal comfort; INDOOR ENVIRONMENT; LOW-COST; MEASUREMENT PROTOCOLS; OFFICE ENVIRONMENTS; FIELD-TEST; QUALITY; AIR; STANDARDS; SATISFACTION; DISTRACTION;
D O I
10.1016/j.buildenv.2018.12.016
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The quality of buildings can be assessed in terms of the indoor air quality, thermal comfort, lighting quality, acoustic comfort afforded the occupants, collectively referred to as Indoor Environmental Quality (IEQ). A major barrier to a more thoroughly representative audit of actual IEQ performance are the expense and complexity of the measurement instrumentation required. Rapid developments in sensor technology in recent years present the opportunity for continuous and pervasive IEQ monitoring to deliver truly representative characterisations of building performance at a modest cost. The last remaining obstacle to realising these developments seems to be a concern about instrument accuracy. In this paper we test the performance of a low-cost IEQ monitoring system (SAMBA) introduced in an earlier paper. Calibration data from 100 devices was analysed to calculate the standard error of the estimate as a measure of equipment accuracy. Those performance specifications were used in a Monte Carlo simulation based on measurements of thermal comfort parameters from 24 office buildings. Performance measures suggests the low-cost system, whilst not as accurate as laboratory equipment, is more than sufficient for building IEQ diagnostics and compliance assessments. Furthermore, the results of the Monte Carlo simulation show that continuous monitoring systems are better at characterising long-term performance than ad hoc measurement strategies using precision equipment. Low-cost pervasive monitoring technologies therefore offer a unique opportunity to improve our quantitative understanding of, and response to, indoor environmental quality issues.
引用
收藏
页码:241 / 252
页数:12
相关论文
共 68 条
[1]  
Abbaszadeh S., 2006, P HLTH BUILDINGS 200, V3, P365
[2]   A review of standards and guidelines set by international bodies for the parameters of indoor air quality [J].
Abdul-Wahab, Sabah Ahmed ;
En, Stephen Chin Fah ;
Elkamel, Ali ;
Ahmadi, Lena ;
Yetilmezsoy, Kaan .
ATMOSPHERIC POLLUTION RESEARCH, 2015, 6 (05) :751-767
[3]  
Al horr Yousef, 2016, International Journal of Sustainable Built Environment, V5, P1, DOI 10.1016/j.ijsbe.2016.03.006
[4]   Open Source Building Science Sensors (OSBSS): A low-cost Arduino-based platform for long-term indoor environmental data collection [J].
Ali, Akram Syed ;
Zanzinger, Zachary ;
Debose, Deion ;
Stephens, Brent .
BUILDING AND ENVIRONMENT, 2016, 100 :114-126
[5]  
[Anonymous], 2013, RP112 ANSIIES
[6]  
[Anonymous], 2007, Indoor Environmental Input Parameters for Design and Assessment of Energy Performance of Buildings Addressing Indoor Air Quality, Thermal Environment, Lighting and Acoustics
[7]  
[Anonymous], 2004, 130321 CEN
[8]  
[Anonymous], 2016, ASHRAE Standard 62.1
[9]  
[Anonymous], 2017, 55 ASHRAE
[10]  
[Anonymous], 2007, ISO 9920