Performance analysis of a novel liquid desiccant-vapor compression hybrid air-conditioning system

被引:32
作者
Li Yinglin [1 ]
Zhang Xiaosong [2 ]
Tan Laizai [3 ]
Zhang Zhongbin [1 ]
Wu Wei [1 ]
Xia Xueying [1 ]
机构
[1] Nanjing Normal Univ, Engn Lab Energy Syst Proc Convers & Emiss Control, Nanjing 210042, Jiangsu, Peoples R China
[2] Southeast Univ, Sch Energy & Environm, Nanjing 210096, Jiangsu, Peoples R China
[3] Nanjing Wuzhou Refrigerat Grp Co Ltd, Nanjing 211100, Jiangsu, Peoples R China
基金
中国博士后科学基金; 美国国家科学基金会;
关键词
Liquid desiccant; Auxiliary regenerator; Solution branch; Concentration difference; SOURCE HEAT-PUMPS; DEHUMIDIFICATION; TEMPERATURE; COMBINATION;
D O I
10.1016/j.energy.2016.03.127
中图分类号
O414.1 [热力学];
学科分类号
摘要
LDCH (Liquid desiccant-vapor compression hybrid) air-conditioning systems are popular for reducing energy consumption. This work tests a conventional LDCH air-conditioning experimental setup and establishes the corresponding mathematical model to analyze the effect of the concentrated solution branch in the SSHE (solution solution heat exchanger) on the cooling capacity of the evaporator; the results show that the percentage of cooling capacity loss of the evaporator exceeds 10% with the small concentration difference of 1.5% in the conventional LDCH air-conditioning system. Afterwards, a new LDCH air-conditioning system is proposed by adopting an auxiliary regenerator to cut down the cooling capacity loss of the evaporator, and the analysis results show that there is a big temperature drop of the concentrated solution branch after being pretreated by the auxiliary regenerator; under the condition of concentration difference of 2.65%, the inlet temperature of concentrated solution branch from the regeneration side in the SSHE can decrease over 6 degrees C; and the extra heat load entering the dehumidification side from the regeneration side obviously decreases. Consequently, the evaporator only needs to spend 1.5% of its cooling capacity on the compensation for the extra heat load. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:180 / 189
页数:10
相关论文
共 21 条
[1]   The effect of absorber packing height on the performance of a hybrid liquid desiccant system [J].
Ani, FN ;
Badawi, EM ;
Kannan, KS .
RENEWABLE ENERGY, 2005, 30 (15) :2247-2256
[2]   On the performances of a hybrid air-conditioning system in different climatic conditions [J].
Bergero, Stefano ;
Chiari, Anna .
ENERGY, 2011, 36 (08) :5261-5273
[3]   Performance analysis of a liquid desiccant and membrane contactor hybrid air-conditioning system [J].
Bergero, Stefano ;
Chiari, Anna .
ENERGY AND BUILDINGS, 2010, 42 (11) :1976-1986
[4]   Performance analysis of a hybrid air-conditioning system dehumidified by liquid desiccant with low temperature and low concentration [J].
Chen, Yao ;
Yin, Yonggao ;
Zhang, Xiaosong .
ENERGY AND BUILDINGS, 2014, 77 :91-102
[5]   Properties of aqueous solutions of lithium and calcium chlorides: formulations for use in air conditioning equipment design [J].
Conde, MR .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2004, 43 (04) :367-382
[6]   Combination of ground source heat pumps with chemical dehumidification of air [J].
Gasparella, A ;
Longo, GA ;
Marra, R .
APPLIED THERMAL ENGINEERING, 2005, 25 (2-3) :295-308
[7]   A new heat pump desiccant dehumidifier for supermarket application [J].
Lazzarin, Renato M. ;
Castellotti, Francesco .
ENERGY AND BUILDINGS, 2007, 39 (01) :59-65
[8]   New type of fresh air processor with liquid desiccant total heat recovery [J].
Li, Z ;
Liu, XH ;
Jiang, Y ;
Chen, XY .
ENERGY AND BUILDINGS, 2005, 37 (06) :587-593
[9]   Survey of liquid desiccant dehumidification system based on integrated vapor compression technology for building applications [J].
Mohammad, Abdulrahman Th. ;
Bin Mat, Sohif ;
Sulaiman, M. Y. ;
Sopian, K. ;
Al-Abidi, Abduljalil A. .
ENERGY AND BUILDINGS, 2013, 62 :1-14
[10]   Survey of hybrid liquid desiccant air conditioning systems [J].
Mohammad, Abdulrahman Th. ;
Bin Mat, Sohif ;
Sulaiman, M. Y. ;
Sopian, K. ;
Al-abidi, Abduljalil A. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2013, 20 :186-200