Fault Analysis of The Distance Protection Overreach Caused by The Power Transmission Lines Ring Closing with A Wrong Phase Sequence

被引:0
作者
He, He [1 ]
Wang, Hongbin [1 ]
Huang, Ruiling [1 ]
机构
[1] State Grid Chongqing Elect Power CO, Elect Power Res Inst, Chongqing, Peoples R China
来源
2021 3RD ASIA ENERGY AND ELECTRICAL ENGINEERING SYMPOSIUM (AEEES 2021) | 2021年
关键词
transmission lines; ring closing; distance protection; overreach;
D O I
10.1109/AEEES51875.2021.9403171
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
A power transmission lines ring closing with a wrong phase sequence occurred in a regional power grid, which led to an overreach of the line distance protection. Through theoretical analysis, it is found that when the lines ring closing is operated with a wrong phase sequence, the protection shows the similar electrical characteristics as the phase-to-phase short circuit, and there is an equivalent phase-to-phase fault point in the system, which is the midpoint of all equivalent impedances between the power supply on both sides. As a result, the equivalent measured impedance may fall into the action range of the distance protection somewhere, which will lead to the exceeding of distance protection. The actual fault data also confirm the analysis conclusion.
引用
收藏
页码:114 / 118
页数:5
相关论文
共 40 条
  • [31] Analysis of the equivalent fault characteristics of DC system and its impact on distance protection based on power-frequency variation
    Cai, Dongxiao
    Li, Haifeng
    Zhu, Xinchi
    JOURNAL OF ENGINEERING-JOE, 2019, (16): : 1275 - 1279
  • [32] Fault Statistics and Analysis of 220-kV and Above Transmission Lines in a Southern Coastal Provincial Power Grid of China
    Chen, Binghuang
    IEEE OPEN ACCESS JOURNAL OF POWER AND ENERGY, 2020, 7 (01): : 122 - 129
  • [33] Modified distance protection of transmission lines originating from DFIG-based WPPs by considering the impact of fault-induced rotor frequency and LVRT requirements
    Zhang, Xiaoyou
    Radwan, Mohamed
    Azad, Sahar Pirooz
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2023, 147
  • [34] Analysis and improvement of mal-operation in distance protection of multi-stage series transmission line with single power source
    Wang H.
    Li Y.
    Zhang Y.
    Wang W.
    Zeng Z.
    Cao L.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2021, 41 (02): : 179 - 185
  • [35] Distributed parameter based distance protection for transmission lines and identification of short-circuit faults under low-, medium-and high resistance at fault point
    Zeng, Huimin
    Lin, Fuhong
    Kang, Xiaojuan
    Dianwang Jishu/Power System Technology, 2014, 38 (01): : 262 - 268
  • [36] Reliable protection for static synchronous series compensated double-circuit transmission lines based on positive sequence active power calculations using PMUs
    Elhabashy, Moustafa M.
    Sharaf, H. M.
    Ibrahim, Doaa Khalil
    ELECTRIC POWER SYSTEMS RESEARCH, 2023, 223
  • [37] Approximate analytic solutions to Radulet equations for the analysis of electromagnetic transients in single-phase power transmission lines
    Mendez Navarro, J. Arturo
    Kaikina, Elena I.
    Ruiz, Hector F.
    Guardado, J. Leonardo
    Castellanos, Alejandro
    NONLINEAR ANALYSIS-REAL WORLD APPLICATIONS, 2011, 12 (04) : 2077 - 2090
  • [38] Fault Analysis and Traveling-Wave-Based Protection Scheme for Double-Circuit LCC-HVDC Transmission Lines With Shared Towers
    Ma, Yanjun
    Li, Haifeng
    Wang, Gang
    Wu, Jiyang
    IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (03) : 1479 - 1488
  • [39] Single-phase grounding distance protection of parallel transmission lines on same poles based on electric quantities data from single terminal and single line
    Bi, Tianshu
    Li, Wei
    Xu, Zhenyu
    Yang, Qixun
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2013, 37 (07): : 88 - 93