The Evaluation Method of Surface Roughness Degree for Long-Term Operating Conductors Based on Gray Value Matrix

被引:8
作者
Liu, Lin [1 ]
Bian, Xingming [2 ]
Cao, Lu [3 ]
Zhuansun, Xu [4 ]
机构
[1] North China Elect Power Univ, Sch Energy Power & Mech Engn, Beijing 102206, Peoples R China
[2] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewabl, Beijing 102206, Peoples R China
[3] Tsinghua Univ, Grad Sch Shenzhen, Shenzhen 518055, Guangdong, Peoples R China
[4] State Grid Shaanxi Elect Power Corp Econ Res Inst, Xian 710065, Shaanxi Provinc, Peoples R China
基金
中国博士后科学基金; 中国国家自然科学基金;
关键词
Gray value matrix; long-term operating conductors; neighborhood averaging method; surface roughness; CORONA CAGE;
D O I
10.1109/TPWRD.2015.2415452
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In order to obtain the average surface roughness R-a of the long-term operating conductors in service, the features of 2-D surface morphologies were investigated based on the gray value matrix G. The neighborhood averaging method was utilized in obtaining G. In a wide range of R-a, a linear relationship was discovered between the variance F and R-a Therefore, R-a could be obtained based on the images from the camera and G without the need to dismantle the conductors in service, and it is more time saving and economical for the measurements.
引用
收藏
页码:1641 / 1643
页数:3
相关论文
共 10 条
[1]   Surface roughness effects on the corona discharge intensity of long-term operating conductors [J].
Bian, X. M. ;
Chen, L. ;
Yu, D. M. ;
Wang, L. M. ;
Guan, Z. C. .
APPLIED PHYSICS LETTERS, 2012, 101 (17)
[2]   Influence of Aged Conductor Surface Conditions on AC Corona-generated Audible Noise with a Corona Cage [J].
Bian, Xingming ;
Chen, Lan ;
Yu, Deming ;
MacAlpine, J. M. K. ;
Wang, Liming ;
Guan, Zhicheng ;
Chen, Fangdong ;
Yao, Wenjun ;
Zhao, Shuzhen .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2012, 19 (06) :2037-2043
[3]   Influence of Aged Conductor Surface Conditions on AC Corona Discharge With a Corona Cage [J].
Bian, Xingming ;
Yu, Deming ;
Chen, Lan ;
MacAlpine, J. M. K. ;
Wang, Liming ;
Guan, Zhicheng ;
Chen, Fangdong .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2011, 18 (03) :809-818
[4]   NATURAL AGING OF NON-ENERGIZED ALUMINUM CONDUCTORS [J].
BOOKER, JR .
IEEE TRANSACTIONS ON POWER DELIVERY, 1986, 1 (04) :269-274
[5]   TEXTURAL FEATURES FOR IMAGE CLASSIFICATION [J].
HARALICK, RM ;
SHANMUGAM, K ;
DINSTEIN, I .
IEEE TRANSACTIONS ON SYSTEMS MAN AND CYBERNETICS, 1973, SMC3 (06) :610-621
[6]  
Ma M. H., 2007, P IEEE C EL INS DIEL, P537
[7]  
Maruvada PS., 2000, CORONA PERFORMANCE H
[8]  
Peek F.W., 1929, DIELECTRIC PHENOMENA, V3rd
[9]   AN EFFICIENT APPROACH TO ESTIMATE FRACTAL DIMENSION OF TEXTURAL IMAGES [J].
SARKAR, N ;
CHAUDHURI, BB .
PATTERN RECOGNITION, 1992, 25 (09) :1035-1041
[10]   AGING EFFECTS OF CONDUCTOR SURFACE CONDITIONS ON DC CORONA CHARACTERISTICS [J].
SUDA, T ;
HIRAYAMA, Y ;
SUNAGA, Y .
IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (04) :1903-1912