Test Plan Automation for Power Transformer Protective Relay Commissioning

被引:0
作者
Quinteros, Milton [1 ]
Allen, Mark [1 ]
Al Marhoon, Hussain [2 ]
Beeravolu, Nagendrakumar [3 ]
机构
[1] Entergy Serv Inc, 639 Loyola Ave L ENT 17B, New Orleans, LA 70113 USA
[2] Univ New Orleans, New Orleans, LA 70148 USA
[3] IK Power Syst Solut Inc, New Orleans, LA 70130 USA
来源
2015 68TH ANNUAL CONFERENCE FOR PROTECTIVE RELAY ENGINEERS | 2015年
关键词
Differential; Power Substation automation; Test Plan; Transformers;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The purpose of this paper is to present the implementation of a computer automated Test-Tool program that efficiently produces relay test plans to commission various microprocessor-based relays used to protect power transformers with and without low-side main breakers. The Test-Tool calculates the necessary currents, voltages and digital control conditions based on an automated read of a specific relay settings file. The Test-Tool is then used to interact with the software of a computer-operated test-set by first transferring this information to the test-set and then by acquiring the results of the tests and providing a customized report. This report presents and summarizes the technical information about the power transformer test procedures and its results. As well as being a quality control tool for consistent and thorough relay testing of power transformer installations, this Test-Tool can be used as training support material for new relay technicians and setting engineers.
引用
收藏
页码:536 / 545
页数:10
相关论文
共 10 条
[1]  
Alexander G., 2013, ENERGIZE, P38
[2]  
[Anonymous], 1996, IEEE POWER SYSTEM RE
[3]   Commissioning numerical relays [J].
Closson, JR ;
Young, M .
CONFERENCE RECORD OF 2001 ANNUAL PULP AND PAPER INDUSTRY TECHNICAL CONFERENCE, 2001, :81-91
[4]   Lessons learned through commissioning and analyzing data from transformer differential installations [J].
Costello, David .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2008, 44 (04) :979-1003
[5]  
Fedirchuk D., 2011, EL POW EN C EPEC 201
[6]  
Fulford S., 2007, P 34 ANN W PROT REL
[7]   Reliability considerations of multifunction protection [J].
Johnson, GF .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2002, 38 (06) :1688-1700
[8]   Multifuction digital relay commissioning and maintenance testing [J].
Mozina, C ;
Young, M .
IEEE INDUSTRY APPLICATIONS MAGAZINE, 2005, 11 (05) :50-58
[9]  
Thompson M. J., 2011, 2011 64th Annual Conference for Protective Relay Engineers, P278, DOI 10.1109/CPRE.2011.6035629
[10]  
Zimmerman K., 2008, PROT REL ENG 2008 61