Analysis on Protection Coordination of Hybrid SFCL With Protective Devices in a Power Distribution System

被引:16
作者
Lim, Sung-Hun [1 ]
Kim, Jin-Seok [1 ]
Kim, Jae-Cul [1 ]
机构
[1] Soongsil Univ, Seoul 156743, South Korea
关键词
Hybrid superconducting fault current limiter (SFCL); over-current relay (OCR); protection coordination; protective device; FAULT CURRENT LIMITER; DESIGN;
D O I
10.1109/TASC.2010.2093593
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Since the hybrid superconducting fault current limiter (SFCL) to solve the problems such as the larger volume of the superconducting components and the slow recovery time after the fault is removed has been developed, the plans to apply the hybrid SFCL into the real electrical power grid have been reported. Especially, the discussion for the protection coordination between the existing protective devices due to the introduction of the hybrid SFCL is more required together with the review from the whole viewpoint of the power system. In this paper, the experimental devices to simulate the operation of the hybrid SFCL as well as the protection coordination between the protective devices such as the over-current relay (OCR) were constructed and the protection coordination of the hybrid SFCL with the protective devices was analysed through the experiments. Through the analysis on the experimental results, among the various components comprising the hybrid SFCL, the current limiting resistor (CLR) was confirmed to affect the protection coordination between the OCR and the hybrid SFCL and the method to keep the protection coordination between the hybrid SFCL and the protective devices was discussed.
引用
收藏
页码:2170 / 2173
页数:4
相关论文
共 9 条
[1]   Introduction of a Hybrid SFCL in KEPCO Grid and Local Points at Issue [J].
Hyun, Ok-Bae ;
Park, Kwon-Bae ;
Sim, Jungwook ;
Kim, Hye-Rim ;
Yim, Seong-Woo ;
Oh, Il-Sung .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2009, 19 (03) :1946-1949
[2]   Reliability Enhancement of the Fast Switch in a Hybrid Superconducting Fault Current Limiter by Using Power Electronic Switches [J].
Hyun, Ok-Bae ;
Sim, Jungwook ;
Kim, Hye-Rim ;
Park, Kwon-Bae ;
Yim, Seong-Woo ;
Oh, Il-Sung .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2009, 19 (03) :1843-1846
[3]   Performance of a high-Tc superconducting fault current limiter - Design of a 6.6kV magnetic shielding type superconducting fault current limiter [J].
Kado, H ;
Ichikawa, M .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 1997, 7 (02) :993-996
[4]   Design and experiments of novel hybrid type superconducting fault current limiters [J].
Lee, B. W. ;
Park, K. B. ;
Sim, J. ;
Oh, I. S. ;
Lee, H. G. ;
Kim, H. R. ;
Hyun, O. B. .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2008, 18 (02) :624-627
[5]   Quench and recovery characteristics of series-connected resistive byte SFCLs with magnetically coupled shunt-reactors [J].
Lim, Sung-Hun ;
Kim, Jae-Chul .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2008, 18 (02) :729-732
[6]   Current Limiting and Recovery Characteristics of SFCLs Using Magnetic Coupling of Two Coils [J].
Lim, Sung-Hun ;
Moon, Jong-Fil ;
Kim, Jae-Chul .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2009, 19 (03) :1900-1903
[7]  
Sung-Hun Lim, 2007, Journal of Electrical Engineering & Technology, V2, P289, DOI 10.5370/JEET.2007.2.3.289
[8]  
Sung-Hun Lim, 2008, Journal of Electrical Engineering & Technology, V3, P213, DOI 10.5370/JEET.2008.3.2.213
[9]   Study on Protection Coordination Between Protective Devices in a Power Distribution System With an SFCL [J].
You, Il-Kyoung ;
Lim, Sung-Hun ;
Kim, Jae-Chul ;
Hyun, Ok-Bae .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2010, 20 (03) :1168-1171