Dynamic Characteristics of a 22.9 kV Hybrid SFCL for Short-Circuit Test Considering a Simple Coordination of Protection System in Distribution Networks

被引:14
作者
Kim, Woo-Seok [1 ]
Hyun, Ok-Bae [1 ]
Park, Chung-Ryul [1 ]
Yim, Seong-Woo [1 ]
Yu, Seung-Duck [1 ]
Yang, Seong-Eun [1 ]
Kim, Hee-Sun [1 ]
Kim, Hye-Rim [1 ]
机构
[1] KEPCO Res Inst, Taejon, South Korea
关键词
Protection coordination; reclosing; superconducting fault current limiter;
D O I
10.1109/TASC.2011.2174950
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents the results of short-circuit tests with a 22.9 kV hybrid superconducting fault current limiter (SFCL) on the KEPCO test grid. The hybrid SFCL we used for the test had suffered from lots of field tests including a long term operation and it is still in working order. We have already proved that the SFCL showed high reliability as well as feasibility through a long term operation and short-circuit tests performed before. In this paper, we tried to study a dynamic characteristics of the same SFCL on the distribution power grid through short-circuit tests with a circuit breaker and a reclosing relay. An artificial fault generator (AFG) was used to generate fault currents in the KEPCO power test center. The two objectives of the tests are (1) verifying a precise reaction of the SFCL to reclosing operation and (2) a study for protection coordination with SFCL. The test results showed that the SFCL worked precisely with a fast recovery of the superconducting elements when we applied a one-time reclosing operation with the interval of 0.6 second. We also suggested a proper manipulation of the coordination of the protection system in distribution networks with the SFCL in the paper.
引用
收藏
页数:4
相关论文
empty
未找到相关数据