Soft starting of large induction motors at constant current with minimised starting torque pulsations

被引:0
作者
Zenginobuz, G [1 ]
Çadirci, I [1 ]
Ermis, M [1 ]
Barlak, C [1 ]
机构
[1] TUBITAK, METU Informat Technol & Elect Res Inst, TR-06531 Ankara, Turkey
来源
IAS 2000 - CONFERENCE RECORD OF THE 2000 IEEE INDUSTRY APPLICATIONS CONFERENCE, VOLS 1-5 | 2000年
关键词
induction motor; soft starter; torque pulsations;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The performance of a voltage-controlled, large induction motor soft starter has been improved, resulting in nearly perfect current and torque profiles. The performance analysis of the soft starter, motor - load combination has been carried out in dynamic state using a hybrid induction machine model which takes account of disconnected, two-phase and three-phase operational modes of the machine. Some simple control strategies have been proposed to keep the current constant at any preset value during starting, and to eliminate supply frequency starting torque pulsations. These are shown to be very effective in the elimination of reclosing transient torque and current components at any speed at the reconnection instant to the supply after an interruption, or at the instant of bus transfer. The proposed strategies have been verified experimentally on a laboratory machine using a special torque measurement system in the dynamic state.
引用
收藏
页码:1593 / 1604
页数:12
相关论文
共 24 条
[1]  
BLAABJERG F, 1997, IEEE IND APPL MAG, P56
[2]  
BOWERFIND J, 1986, IEEE T IND APPL JAN, P109
[3]  
BRUCE FM, 1984, IEEE T IND APPL JAN, P46
[4]   A solid state direct on line starter for medium voltage induction motors with minimized current and torque pulsations [J].
Çadirci, I ;
Ermis, M ;
Nalçaci, E ;
Ertan, B ;
Rahman, M .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1999, 14 (03) :402-412
[5]  
COLLERAN PJ, 1983, IEEE T IND APPL NOV, P1014
[6]   EFFECTS OF MOMENTARY VOLTAGE DIPS ON THE OPERATION OF INDUCTION AND SYNCHRONOUS MOTORS [J].
DAS, JC .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1990, 26 (04) :711-718
[7]   ANALYSIS OF TRANSIENT ELECTRICAL TORQUES AND SHAFT TORQUES IN INDUCTION-MOTORS AS A RESULT OF POWER-SUPPLY DISTURBANCES [J].
DAUGHERTY, RH .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (08) :2826-2836
[8]   ANALYSIS AND APPLICATION OF 3-PHASE INDUCTION-MOTOR VOLTAGE CONTROLLER WITH IMPROVED TRANSIENT PERFORMANCE [J].
DELEROI, W ;
WOUDSTRA, JB ;
FAHIM, AA .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1989, 25 (02) :280-286
[9]   Performance analysis of fast reclosing transients in induction motors [J].
Faiz, J ;
Ghaneei, M ;
Keyhani, A .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1999, 14 (01) :101-107
[10]   ANALYSIS OF VARIABLE-VOLTAGE THYRISTOR CONTROLLED INDUCTION-MOTORS [J].
HAMED, SA ;
CHALMERS, BJ .
IEE PROCEEDINGS-B ELECTRIC POWER APPLICATIONS, 1990, 137 (03) :184-193